Chapter 4. Browser Operation
29
PDU Status
All eco PDU models support PDU device level monitoring. The
PDU Status
section allows you to set up a power management configuration for the PDU
device as a whole:
PDU Threshold Settings
These fields are used to set the maximum, minimum, and fluctuation
threshold settings for Aggregate Current, Voltage, Power, and Aggregate
Power Dissipation. If a range falls below the minimum setting, or exceeds
the maximum setting an alarm is triggered.
Breaker
status (ON / OFF) displays here.
Voltage Frequency
is displayed here in Hz.
On / Off / Reboot
You can manually turn the device On and Off from this page by clicking
the radio buttons.
If you wish to reboot the device, check the Reboot checkbox and click the
Off
button beside the checkbox.
Sensor 1 / Sensor 2
If you have sensors installed in your installation, use these fields to set the
maximum, minimum, and fluctuation threshold settings for Temperature,
Humidity, and Differential Pressure.
Note:
Sensors are optional accessories. Check with your dealer for
information about NRGence eco Sensors software.