eco PDU PE Series User Manual
32
Power On Time Schedule Settings
Check the
Enable Power On Time Schedule
box to use the
Power ON
Delay
setting to set the amount of time the eco PDU waits before powering
on an outlet. See
Power ON Delay
in the table below.
Buzzer Setting
Checking the
Enable Buzzer Alarm
box sounds an alarm and sends
SNMP trap or e-mail alerts when a circuit breaker trips or a PDU/Outlet
threshold setting exceeds the minimum or maximum setting.
Outlet Configuration
The
Outlet Configuration
section lets you set the power management settings
for each outlet on the PDU.
Heading
Meaning
Outlet Name
Each outlet can be given a distinctive name. The maximum
number of characters is 15.
Confirmation
Required
If this option is enabled (there is a check in the checkbox), a dialog
box comes up asking you to confirm a power operation before it is
performed. If it is disabled (there is no check in the checkbox), the
operation is performed without confirmation.
Power ON Delay
Sets the amount of time the eco PDU waits after the Power Button
is clicked (see
, page 30), before it turns on the power
to the outlet. You must check the
Enable Power On Time Schedule
Setting
box for this setting to take effect. See
Note:
The default delay time is 0 seconds; the maximum is 999 seconds.
When a series of outlets are scheduled to be powered up, they turn on in
sequence with a default delay of 10 milliseconds between each outlet.
Power OFF Delay Sets the amount of time the eco PDU waits after the Power Button
is clicked (see
, page 30), before it turns off the power
to the outlet.
For the
System after AC Back
option (see below), after the delay
time expires, the eco PDU waits another fifteen seconds, then
shuts the computer down.
The default delay time is 15 seconds. The maximum delay time is
999 seconds.