PN7212 / PN7320 User Manual
158
Administrator Login Failure
If you are unable to perform an Administrator login (because the Username and
Password information has become corrupted, or you have forgotten it, for
example), you can clear the login information with the following procedure:
1. Power off the PN7212 / PN7320 and remove its housing.
2. Short the jumper labeled J5.
3. Power on the switch.
4. When the Link and 10/100Mbps LEDs flash, power off the switch.
5. Remove the jumper cap from J6.
6. Close the housing and start the PN7212 / PN7320 back up.
After you start back up, you can use the default Username and Password
(see
, page 19) to log in.