Chapter 4. LCD/Button Operations
33
UPS Setting
There are two parameters for the UPS as displayed in the picture below:
Parameter 1: The number shown here determines the settings you can
adjust. Please refer to the table below for the settings.
Parameter 2: The number shown here is the option or value for the
settings determined in parameter 1.
Parameter 1 & Interface Display
Parameter 2 Description
Output Voltage Setting
Display:
01
Parameter 2: Output voltage
For 200/208/220/230/240 VAC models, you
may choose the following output voltages:
200:
200vac output voltage
208:
208vac output voltage
220:
220vac output voltage
230:
230vac output voltage (Default)
240:
240vac output voltage
For 100/110/115/120/127 VAC models, you
may choose the following output voltages:
100:
100vac output voltage
110:
110vac output voltage
115:
115vac output voltage
120:
120vac output voltage (Default)
125:
125vac output voltage
127:
127vac output voltage (not applicable
for U.S. region)
Summary of Contents for NRGence HV Series
Page 10: ...UPS User Manual x This Page Intentionally Left Blank...
Page 16: ...UPS User Manual 6 UPS HV Series Rear View...
Page 22: ...UPS User Manual 12...
Page 24: ...UPS User Manual 14 4 Replace the front panel back to the unit...
Page 29: ...Chapter 2 Hardware Setup 19 3 Replace the front panel back to the unit...
Page 36: ...UPS User Manual 26 This Page Intentionally Left Blank...
Page 58: ...UPS User Manual 48 This Page Intentionally Left Blank...