Chapter 4. LCD/Button Operations
35
ECO Voltage Range Setting
Display: 05
Display: HS
Parameter 2: Acceptable high voltage
point and low voltage point for ECO
mode.
Press the Up or Down key to adjust
the values.
HLS:
High loss voltage in ECO mode in
parameter 2.
For 200/208/220/230/240 VAC models, the
setting range for parameter 3 is +7V to +24V
of the nominal voltage. (Default: +12V)
For 100/110/115/120/127 VAC models, the
setting range for parameter 3 is +3V to +12V
of the nominal voltage.
(Default: +6V)
LLS:
Low loss voltage in ECO mode in
parameter 2.
For 200/208/220/230/240 VAC models, the
setting range for parameter 3 is -7V to -24V
of the nominal voltage.
(Default:
-
12V)
For 100/110/115/120/127 VAC models, the
setting voltage for parameter 3 is -3V to -12V
of the nominal voltage.
(Default: -6V)
Enable/Disable Bypass when UPS
is off
Display: 06
Parameter 2: Enable or disable
Bypass
function.
You may choose the following two options:
ENA:
Enable bypass
DIS:
Disable bypass (Default)
Parameter 1 & Interface Display
Parameter 2 Description