UPS User Manual
58
Total Outlets
8
9
Outlet Type
(8) NEMA 5-15R
NEMA 5-20R
(8) NEMA
5-20R +
(1) NEMA
L5-30R
Outlets - Battery &
Surge Protected
8
9
Rated Power
Factor
>0.96
0.97
0.96
Crest Factor
3:1
Harmonic
Distortion
≦
2 % THDv (Linear Load)
≦
4 % THDv (Non-linear Load)
Voltage Regulation
± 1% (Batt)
Transfer Time (AC
to Batt.)
0ms
Transfer Time
(Inverter to Bypass)
4ms (ECO)
Battery
Runtime at Half
Load (min)
Half load
10.1
Half load
12.9
Half load
10.3
Half load
10.0
Half load
12.8
Half load
10.1
Runtime at Full
Load (min)
Full load
2.95
Full load
4.44
Full load
2.96
Full load
2.95
Full load
4.37
Full load
2.96
Battery Type
Sealed Lead-Acid
Battery Pack
Voltage
24V
36V
36V
48V
72V
72V
Battery Size
12V/9AH 12V/7AH 12V/9AH 12V/9AH 12V/7AH 12V/9AH
Battery Quantity
2
3
3
4
6
6
Hot-Swappable
Yes
Typical Recharge
Time
3 hours recover to 95% capacity @2A charging current. Max
charger current 8A
Extended Battery
Module
BP24V18
AH
BP36V18
AH
BP36V18
AH
BP48V18
AH
BP72V18
AH
BP72V18
AH
Aten Model Name
OL1000
LV
OL1000
SLV
OL1500
LV
OL2000
LV
OL2000
SLV
OL3000
LV
Summary of Contents for NRGence HV Series
Page 10: ...UPS User Manual x This Page Intentionally Left Blank...
Page 16: ...UPS User Manual 6 UPS HV Series Rear View...
Page 22: ...UPS User Manual 12...
Page 24: ...UPS User Manual 14 4 Replace the front panel back to the unit...
Page 29: ...Chapter 2 Hardware Setup 19 3 Replace the front panel back to the unit...
Page 36: ...UPS User Manual 26 This Page Intentionally Left Blank...
Page 58: ...UPS User Manual 48 This Page Intentionally Left Blank...