UPS User Manual
34
Output Frequency Setting
Display: 03
Parameter 2: Output frequency.
You may set the initial frequency on battery
mode:
BAT 50:
50Hz output frequency
BAT 60:
60Hz output frequency
If converter mode is enabled, you may
choose the following output frequencies:
CF 50:
50Hz output frequency
CF 60:
60Hz output frequency
Enable/Disable ECO
Display: 04
Parameter 2: Enable or disable
ECO
function.
You may choose the following two options:
ENA:
Enable ECO mode
DIS:
Disable ECO mode (Default)
ECO Voltage Range Setting
Display: 05
Display: HS
Parameter 2: Acceptable high voltage
point and low voltage point for ECO
mode.
Press the Up or Down key to adjust
the values.
HLS:
High loss voltage in ECO mode in
parameter 2.
For 100/110/115/120/127 VAC models, the
setting range for parameter 3 is +3V to +12V
of the nominal voltage.
(Default: +6V)
LLS:
Low loss voltage in ECO mode in
parameter 2.
For 100/110/115/120/127 VAC models, the
setting voltage for parameter 3 is -3V to -12V
of the nominal voltage.
(Default: -6V)
Parameter 1 & Interface Display
Parameter 2 Description