38
Charger Boost Voltage Setting
Display 14
Parameter 2: Charger boost voltage.
2.25-2.40:
setting the charger boost voltage
from 2.25 V/cell to 2.40V/cell. (Default:
2.36V/cell)
Charger Float Voltage Setting
Display: 15
Parameter 2:
Charger float voltage.
2.20-2.33:
Set the charger float voltage from
2.20 V/cell to 2.33V/cell. (Default: 2.28V/cell)
EPO Logic Setting
Display: 16
Parameter 2:
EPO function control logic.
AO:
Active Open (Default). When selected, it
will activate EPO function with Pin 1 and Pin
2 in open status.
AC:
Active Close. When selected, it will
activate EPO function with Pin 1 and Pin 2 in
close status.
Enable/Disable Site Fault
Detection
Display: 17
Parameter 2: Enable/disable sit fault
detection.
ENA:
Enable (Default).
DIS:
Disable.
Parameter 1 & Interface Display
Parameter 2 Description