Sheet # 692/1u –
Electric connectors (F610)
Version 1.04a
User guide
ATEQ 6th series
Page 3/7
3.2.2. Connector in Profibus mode
1
5
9
6
Profibus
: SubD 9 points female connector.
Pin 1
PE (ground)
Pin 4
CNTR – A (repeater
control signal)
Pin 7
Not used
Pin 2
Not used
Pin 5
DGND (logic ground)
Pin 8
Data Line B
Pin 3
Data Line A
Pin 6
VP (supply)
Pin 9
Not used
3.3. D
EVICENET
,
P
ROFINET OR
E
THERNET
C
ONNECTORS
(
OPTION
)
3.3.1. Devicenet Input (option)
2
1
4
3
5
To connect to others
ATEQ
devices (M12 male connector).
3.3.2. J2 Devicenet output (option)
2
1
4
3
5
To connect to others
ATEQ
devices (M12 female connector).
3.3.3. Wiring Devicenet
Pin 1
Drain
Pin 3
V-
Pin 5
CAN_L
Pin 2
V+
Pin 4
CAN_H
3.3.4. Input and output Profinet
4
3
1
2
5
Ethernet / M12 pin assignement.
M12 female, D coded.
Pin 1
Ethernet Tx + (Transmit Data +)
Pin 3
Ethernet Tx - (Transmit Data -)
Pin 2
Ethernet Rx + (Receive Data +)
Pin 4
Ethernet Rx - (Receive Data -)
Pin 5
Not used