TECHNICAL CHARACTERISTICS
Electrical
Typical Consumption: 15mA (12/24V) and 10mA (48V)
Best resolution in the measures: 1%
The 12/24 volts series model automatically recognise the nominal operation voltage.
The equipment is factory configured as PbA mode and capacity 200Ah , except the model
LEO1 30A, configured for 1000Ah batteries.
The conductors section is important to avoid possible voltage drops that could
cause a bad operation of the system. No drop higher than 3% of the nominal
voltage can be accepted in conditions of maximum intensity.
To calculate the necessary section you can use:
Where 'L' is the line length in meters, 'Imax' is the maximum intensity , and 'c' is the maximum
voltage drop authorised.
ü
ü
ü
Note1: Programmable. The high voltage alarm will be 0,03 V./elem. higher than the charge final
voltage.
Note2: Plus, according to the charge historic of the battery.
Note3: Programmable. The low voltage alarm will be 0,05 V./elem. Higher than the voltage of
consumption unplugging.
Rank of Working Temperature: -5..+40 ºC
Model 12/24 v.
Model 48 v.
Handling Voltage at 25ºC (77ºF)
12 v.
24 v.
48 v.
C100
14,5
29 ,0
58
C50
14,6
29,2
58,4
C20
15
30 ,0
60
Charge Final Voltage (note1)
C10
15,1
30,2
60,4
Initial floating range (note2)
Initial floating range (note2)
13,6-13,9
27,2-27,8
54,4-55,6
Regulation restart voltage and
Regulation restart voltage and
Output floating
Output floating
12,9
25,8
51,6
Consumption restart voltage (programmable)
Consumption restart voltage (programmable)
12,5
25,0
50
C100
11,4
22,8
45,6
C50
11
22
44
C20
10,9
21,8
43,6
M
O
D
E
P
b
A
Output consumption unplugging
Output consumption unplugging
(Note3)
(Note3)
C10
10,8
21,6
43,2
Charge Final Voltage (note1)
13,9
27,8
55,6
13,6-13,9
27,2-27,8
54,4-55,6
12,9
25,8
51,6
12,5
25
50
C100
11,4
22,8
45,6
C50
11
22
44
C20
10,9
21,8
43,6
M
O
D
E
F
L
O
C10
10,8
21,6
43,2
c
5 6
I
L
2
S e c t i o n
M A X
´
´
´
=
DIGITAL CHARGE REGULATOR
LEO1
08
MU-12-L