background image

                                                                     
 
                                       

OPTIMUM GS MODULES INSTALLATION MANUAL

                                                                     

 

Page 14 

Aplicaciones Técnicas de la Energía S.L. (ATERSA) 

www.atersa.com – atersa@elecnor.com   

Madrid (Spain) +34 915 178 452 - Valencia (Spain) +34 961 038 430 

 

7.

 

Wiring 

 

These  modules  contain  factory  installed  bypass  diodes.  If  these  modules  are 

incorrectly connected to each other, the bypass diodes, cables, or junction box may be 

damaged. 

 

Modules  can  be  wired  in  series  to  increase  voltage.  Connect  wires  from  positive 

terminal  of  one  module  to  the  negative  terminal  of  the  next  module.  All  modules 

connected in series should be of the same model number and/or type. 

 

Use    system    wiring    with    suitable    cross-sectional    areas    and    connectors   

that    are    approved    for    use at the maximum short-circuit current of the module. 

 

The  maximum  open  circuit  voltage  of  the  system  must  not  be  greater  than  the 

specified maximum system voltage for the module. 

 

When reverse currents can exceed the value of the maximum protective fuse marked 

on the back of the module, a properly rated and certified over current device (fuse or 

circuit breaker) must be connected in series with each module or string of modules. 

 

Match the polarities of cables and terminals when making the connections; failure to 

do so may result in damage to the module. 

 

Connecting modules in reverse polarity to a high current source, such as a battery, will 

destroy the bypass diodes and render the module inoperative. Bypass diodes are not 

user replaceable. 

 

The junction box is under no circumstances being opened. Opening the junction box 

may void the warranty. 

 

Modules  with  a  suspected  electrical  problem  should  be  returned  to  Atersa  for 

inspection and possible repair or replacement as per the warranty conditions provided 

by Atersa. 

 

For  field  connections, use the minimum No. #12  AWG copper wires  insulated for a 

minimum of 90°C and Sunlight resistant as well. 

 

The minimum and maximum outer cable diameters of the cable are 5 to 7mm 

Ensure proper system operation and maintain the warranty, be careful to observe the correct 

cable connection polarity when connection the module to a battery or to other module. 

 

Series method 

Photovoltaic modules are manufactured to support high voltages. The maximum voltage of 

the system is indicated on the label of the module’s characteristics. Therefore, modules can be 

connected in series until that voltage is reached 

Summary of Contents for OPTIMUM A-235P GS

Page 1: ...ATION MANUAL Page 1 Aplicaciones T cnicas de la Energ a S L ATERSA www atersa com atersa elecnor com Madrid Spain 34 915 178 452 Valencia Spain 34 961 038 430 OPTIMUM GS Modules Installation Manual Re...

Page 2: ...ty 4 Precaution for unpacking handling storage 5 Warning 6 Installation 6 1 Mechanical Installation 6 1 1 Bolting method 6 1 2 Clamping method 6 2 Electrical Connections 6 2 1 Equipment Grounding 6 2...

Page 3: ...f or in any way connected with such installation operation use or maintenance No responsibility is assumed by Atersa for any infringement of patents or other rights of third parties which may result f...

Page 4: ...shall comply with national regional and local codes laws and standards PV modules should be installed and maintained by qualified personnel Only installation service personnel should have access to t...

Page 5: ...s to avoid injury by a slipping module cuts by the edge of a frame etc Do not leave the module unsupported or unsecured prior to installation For example wind can cause a module which is leaning again...

Page 6: ...lation of PV modules Use module for its intended function only Be sure that all other system components are compatible and they do not subject the module to mechanical or electrical hazards Do not tou...

Page 7: ...the southern hemisphere The assembly is to be mounted over a fire resistant roof covering rated for the application The roof slope should be less than 5 in ft less than 22 62 to maintain fire class r...

Page 8: ...not accessible to children or small animals to ensure personal safety and to prevent PV module from damage The junction box shall be in the uppermost position to minimize the ingress of water Clearan...

Page 9: ...oints The hardware required to mount the module is given below Stainless steel M8 304 bolt Stainless steel M8 304 washer Stainless steel M8 304 nut We recommend using a torque wrench for installation...

Page 10: ...lecnor com Madrid Spain 34 915 178 452 Valencia Spain 34 961 038 430 6 1 2 Clamping method For the clamping method is recommended use clamps with figure s sizes The hardware used is the same as boltin...

Page 11: ...OPTIMUM GS MODULES INSTALLATION MANUAL Page 11 Aplicaciones T cnicas de la Energ a S L ATERSA www atersa com atersa elecnor com Madrid Spain 34 915 178 452 Valencia Spain 34 961 038 430...

Page 12: ...OPTIMUM GS MODULES INSTALLATION MANUAL Page 12 Aplicaciones T cnicas de la Energ a S L ATERSA www atersa com atersa elecnor com Madrid Spain 34 915 178 452 Valencia Spain 34 961 038 430...

Page 13: ...mm grounding holes 5 1mm to ground the anodized frame 10 12 AWG exposed copper wire is recommended as Ground wire The fastening system must be spliced with a cable that has a minimum diameter of 2 5m...

Page 14: ...ed in series with each module or string of modules Match the polarities of cables and terminals when making the connections failure to do so may result in damage to the module Connecting modules in re...

Page 15: ...or the corresponding equipment to which the module are connected A cable with an adequate section for the conduction of the total current generated by the modules should be used In all case the conduc...

Page 16: ...Always wear rubber gloves for electrical insulation while maintaining washing or cleaning modules Appropriate electrically insulating Personal Protective Equipment PPE must be worn during any cleaning...

Page 17: ...permanent damage to the glass such as white efflorescence otherwise known as glass disease which may cause reduced power output To avoid dirt accumulation or white efflorescence due to water accumulat...

Page 18: ...rsa com atersa elecnor com Madrid Spain 34 915 178 452 Valencia Spain 34 961 038 430 9 Checklists All fastenings are tight and secure and free of corrosion All cable connections are secure tight clean...

Page 19: ...STC Irradiance of 1000 W m2 AM1 5 spectrum and a cell temperature of 25 C The tolerance of Electrical Characteristics is less than 10 under Standard Test Conditions 2 1 Polycrystalline module Module A...

Page 20: ...ort circuit current A 8 54 8 71 8 84 8 90 8 97 9 05 9 10 9 13 Max power point current A 8 04 8 17 8 28 8 35 8 42 8 49 8 56 8 04 Efficiency 14 5 14 8 15 1 15 4 15 7 16 0 16 3 14 5 2 2 Monocrystalline m...

Page 21: ...9 08 Max power point current A 8 00 8 04 8 11 8 20 8 25 8 34 8 42 8 51 Efficiency 14 4 14 8 15 1 15 4 15 7 16 0 16 3 16 6 Notes Maximum System Voltage 1000V Nominal Operating Cell Temp NOCT 46 2 C Te...

Reviews: