www.atestgaz.pl
7.7.3.3 Simulation of alarms for LPG gas (S2 alarms)
Simultaneous depressing the arrow buttons
(see Figure 1) and holding them depressed for about four
seconds switches the detector over to the simulation mode for LPG gas (S2 alarm). Please remember that
that simulation mode is available only for detectors where collaboration with Teta MiniDet detectors is
enables (HE parameter is set to 1). The simulation procedure is carried out in the same way as for S1 alarms,
but alarms are generated for the Teta MiniDet detector.
The simulation mode (S2) is quitted automatically after the simulation is completed or upon simultaneous
depressing the both arrow buttons
.
7.7.3.4 Test of safety functions
Execution of the test for safety functions is recommended once a year. Test gas is supplied to one unit of
each detector type and response of all components within the Gas Safety System is checked together with
all collaborating systems (e.g. ventilation).
Test of safety function must be executed without approaching of a magnet to gas detector or
initiation of alarm simulations.
7.7.4
Maintenance
Gas detectors should be cleaned only by wiping its housing with a soft damp cloth. Cleaning agents
containing solvents, white spirit, extraction naphtha or alcohols are not allowed.
The device needs no other maintenance beside cleaning external surface of the housing. These surfaces
should be wiped with a soft cloth moistened with water and slight amount of a mild detergent.
7.8
Disposal
This symbol on a product or on its packaging indicates that the product
must not be disposed of with other household waste. Instead, it is the
user's responsibility to ensure disposal of waste equipment by handing it
over to a designated collection point for the recycling of waste electrical
and electronic equipment. The proper recycling of your waste equipment
at the time of disposal will help to conserve natural resources and ensure
that it is recycled in a manner that protects human health and the
environment. Information about relevant designated collection points can
be obtained from the Local Authority, waste disposal companies and in
the place of purchase. The equipment can also be returned to the
manufacturer.
s. 18|20
User Manual: POD-046-ENG R01