ATI
MetriNet Ethernet/IP Communications Manual
17
O&M Manual
Rev-A (6/19)
Sensor 7 MEASURE
Bytes
Data Type
Description
164-167
DINT
S7 Main Value
168-171
DINT
S7 Units
172–175
DINT
S7 Raw Value
176–179
DINT
S7 Temperature
180-181
INT
S7 Output Value
182-183
WORD
S7 Status 1
184-185
WORD
S7 Status 2
186-187
INT
S7 ID
Sensor 8 MEASURE
Bytes
Data Type
Description
188-191
DINT
S8 Main Value
1
192-195
DINT
S8 Units
2
196–199
DINT
S8 Raw Value
1
200–203
DINT
S8 Temperature
1
204-205
INT
S8 Output Value
3
206-207
WORD
S8 Status 1
5
208-209
WORD
S8 Status 2
5
210-211
INT
S8 ID
4
Notes on MEASURE data –
1
Main Value, Raw Value, are Temperature are all 32 bit integers, displayed with an implied
fixed-decimal point 0.000 resolution.
So, 14.00 pH will show as 14000, which means 14.000 pH. 2000 uS conductivity will show as
2000000, meaning 2000.000 uS. 25C will show as 25000 meaning 25.000.
2
Units are stored as packed ASCII hi/lo bytes.
3
Output Value is also displayed with implied 0.000 resolution. The MetriNet has no actual
hardware level output for these voltages. So, these are virtual values, like the alarm setpoints,
that could be used to feed some other process digitally.
4
ID not implemented at this time.