VARMAX TWIN -
Installation, Use and Maintenance
4. INSTALLATION
4.6. Positioning the air
fi
lters and the
fi
ltering layers
!
IMPORTANT:
The air
fi
lters provided with the generators MUST be installed.
The air fi lters must be installed before the gas lines are connected.
Refer to the VARMAX generator's installation, usage and maintenance
manual, paragraph "4-1 Positioning the air fi lter and the layer").
4.7. Installing the boiler
The VARMAX TWIN boilers must not be installed on an fl ammable surface
(wooden fl oor, plastic fl oor covering, etc.).
Recommended distances relative to walls and ceiling:
Suffi
cient clearances must be provided to permit easy maintenance
operations on the boilers.
The
minimum
values (in mm) are indicated in fi gure 2 and in the table below.
A*
B*
C
H
MODELS
550
450
600
263
640
450
600
263
780
450
700
427
900
450
700
427
The greyed out zone above the boiler must remain free of any obstacles
to enable the burner to be inspected and cleaned.
These values cannot be substituted for the speci
fi
c regulatory
requirements.
fi gure 2 - Peripheral clearance
H
A
B
C
450
±10