VARMAX TWIN -
Installation, Use and Maintenance
!
IMPORTANT:
Con
fi
gure the switches on the AVS75 extension module.
Diagrams: VX210 / VX220
page 4 / 8
D. SPECIFIC START-UP PROCEDURE
Make the accessories' electrical connections.
Start up the generator on its own.
Make the following settings:
On generator No. 1
Line No.
Value
• Time and date
menu
Set the time
Hour / minute (1)
HH.MM
Set the date
Day / month (2)
DD.MM
Set the year
Year (3)
YYYY
• Con
fi
gure the isolating valve and its end of run:
Confi guration
menu
Valve command
Relay output QX3 (5892) K37 exhaust fl ap
End of run
Input H5 (5977) Exhaust fl ap info
return
• Confi guration
menu
Confi
gure the DHW pump
(VX210
diagram)
Relay output QX2 (5891)
DHW pump/valve Q3
Confi
gure the Q15 pump
(VX220
diagram)
Relay output QX2 (5891)
Consumption circuit
pump 1 Q15
Confi gure the TWIN B10 output sensor
BX2 sensor input (5931)
Common fl ow sensor
B10
Confi gure the H1 input
(VX220 diagram)
H1 input function (5977)
Consumption circuit 1
request
Confi gure the extension module
Extension module 1 function 1 (6020)
Heating circuit 1
• Con
fi
gure as generator No. 1:
LPB network
menu
Appliance number
Appliance address (6600)
1
Segment number
Segment address (6601)
0
Adjust the bus supply
Bus supply function (6604)
Automatic
Adjust the clock rate
Clock operation (6640)
Master