Ventilation: the inlet grids and ventilation fan should be installed in such a way that any
recirculation of cooling air to the compressor or dryer is avoided.
The air velocity to the grids must be limited to 5 m/s (200 in/s).
The required ventilation capacity to limit the temperature of the compressor room can be
calculated from the following formula:
Q
v
= 0.92 N / ΔT
Q
v
= Required ventilation capacity in m
3
/s
N = Shaft input of compressor in kW
ΔT = Temperature increase in the compressor room in °C
5
Position of the mains cable entry.
6
The drain pipes to the drain collector must not dip into the water of the drain collector.
4.2
Dimension drawings
The dimension drawing can be found in the technical documentation supplied with the unit.
Dimension drawing
Model
9828 0837 16
G 15L, G 18, G 22 Pack, floor-mounted
9828 0837 17
G 15L, G 18, G 22 Pack, tank-mounted
9828 0837 52
G 15L, G 18, G 22 Full-Feature, floor-mounted
9828 0837 53
G 15L, G 18, G 22 Full-Feature, tank-mounted
Text on drawings
Translation or explanation
Emergency stop switch
Emergency stop switch
Power supply
Power supply
Cooling air and compressor inlet
Cooling air and compressor inlet
Cooling air outlet of compressor and motor
Cooling air outlet of compressor and motor
Service panel
Service panel
Compressor controller
Compressor controller
Oil level indicator
Oil level indicator
Compressed air outlet (G1/2” Female)
Compressed air outlet
Forklift openings
Forklift openings
Valve rotation
Valve rotation
Center of gravity
Center of gravity
Cubicle door fully open
Cubicle door fully open
Anchorpoints in base
Anchorpoints in base
Air receiver safety valve
Air receiver safety valve
Vessel anchor points
Vessel anchor points
Air receiver manual drain (G3/8” Female)
Air receiver manual drain
Dryer dewpoint indicator
Dryer dewpoint indicator
Condensate drain integrated dryer
Condensate drain integrated dryer
Dryer inlet cooling air
Dryer inlet cooling air
Instruction book
46
2920 7119 21