G 15L
G 18
G 22
Frequency
(Hz)
Voltage
(V)
Cable size
Cable size
Cable size
60
230
50 mm
2
/ 25 mm
2
50 mm
2
/ 35 mm
2
70 mm
2
/ 35 mm
2
60
380
16 mm
2
/ 10 mm
2
25 mm
2
/ 16 mm
2
35 mm
2
/ 16 mm
2
60
460
16 mm
2
/ 10 mm
2
25 mm
2
/ 10 mm
2
25 mm
2
/ 16 mm
2
CSA/UL
60
200
AWG3
AWG1
AWG1/0
60
230
AWG3
AWG2
AWG1/0
60
460
AWG8
AWG6
AWG6
60
575
AWG8
AWG8
AWG6
9.2
Settings for overload relay and fuses
Fuse calculations
Fuse calculations for IEC are done according to 60364-4-43 electrical installations of buildings,
part 4: protection for safety- section 43: protection against overcurrent. Fuse sizes are calculated
in order to protect the cable against short circuit. Fuse type aM is recommended but gG/gL is
also allowed.
For UL designed machines, calculations of fuses are done according to UL508A (Industrial
control panels).
For CSA, calculations of fuses are done according to CSA 22.2 (Canadian electrical code).
Fuse size is the maximum fuse size in order to protect the motor against short circuit.
• For CSA: fuse HRC form II
• For UL: fuse class J or RK5
If the local conditions are more severe then the described standard conditions, the fuses for worst
case conditions should be used.
Pack version
Frequency
(Hz)
Voltage (V) G 15L
G 18
G 22
IEC
Overload
relay FM1
(A)
Fuses FU
(aM/gG)
Overload
relay FM1
(A)
Fuses FU
(aM/gG)
Overload
relay FM1
(A)
Fuses FU
(aM/gG)
50
230
36.0
63A / 80A
43.5
80A / 100A 50.4
100A /
100A
50
400
20.6
40A / 40A
25.2
50A / 50A
29.0
63A / 63A
60
380
21.7
40A / 50A
25.9
50A / 63A
30.5
63A / 80A
60
460
18.3
40A / 40A
22.1
40A / 40A
25.9
50A / 50A
Instruction book
78
2920 7119 21