Interval
Running hours
Operation
Weekly
50
Check pressure gauge (2). If the pressure reaches 2 bar(e) (29 psig)
or every 6000 operating hours, replace filter (3): Unscrew the filter. Fill
the new filter with water, lightly oil its gasket, screw it on and tighten by
hand (approx. half a turn). Check strainer (5); if necessary, clean it.
Monthly
200
Check the oil level in collector (4). If nearly full, disconnect oil tube (8)
and deliver the oil to the local oil collection service. Reinstall an empty
collector.
“
“
Check pre-filter (10), clean it if necessary.
4.4
Pictographs
Pictographs shown on OSD
Reference
Description
1
Oil
2
Oil outlet
3
Condensate outlet
4
Pressure
5
Inlet
6
Service point drain
7
Separator inlet pressure
8
Oil gasket, screw on filter and tighten by hand (approx. half a turn)
9
Consult instruction leaflet before maintenance or repair
Instruction book
2920 1634 04
61