Protections
Minimum
setting
Factory
setting
Maximum
setting
Compressor element outlet temperature
(shut-down warning level)
˚C
110
119
Compressor element outlet temperature
(shut-down level)
˚C
111
120
120
Service warning
Also see section Preventive maintenance schedule.
Consult Atlas Copco if a timer setting has to be changed. The intervals must not exceed the
nominal intervals and must coincide logically. See section
Calling up/modifying service timer.
Terminology
Term
Explanation
ARAVF
Automatic restart after voltage failure. See section
Compressor
element outlet
The regulator does not accept illogical settings, e.g. if the warning level is programmed
at 95 ˚C/203 ˚F, the minimum limit for the shut-down level changes to 96 ˚C/204 ˚F. The
recommended difference between the warning level and shut-down level is 10 ˚C/18 ˚F.
Delay at shut-
down signal
Is the time for which the signal must exist before the compressor is shut down. If it is
required to program this setting to another value, consult Atlas Copco.
Power recovery
time
Is the period within which the voltage must be restored to have an automatic restart. Is
accessible if the automatic restart is activated.
the automatic restart function, consult Atlas Copco.
Minimum stop
time
Once the compressor has automatically stopped, it will remain stopped for the minimum
stop time (approx. 20 seconds), whatever happens with the net air pressure. Consult
Atlas Copco if a setting lower than 20 seconds is required.
Unloading/
Loading pressure
The regulator does not accept illogical settings, e.g. if the unloading pressure is
programmed at 7.0 bar(e)/101 psig, the maximum limit for the loading pressure changes
to 6.9 bar(e)/100 psig. The recommended minimum pressure difference between
loading and unloading is 0.6 bar/9 psig.
Instruction book
API451763