Ref.
Description
K22
Star contactor
K23
Delta contactor
K34
Relay
Q1
Circuit breaker
T1/2
Transformers
1X3
Terminal strip
4.7
Electrical cable size
Cable size
All cables should be mounted on a horizontal ventilated (with spacing) tray.
Connect cables in the cubicle with the correct cable lugs.
Spacing of 10 mm between naked cable parts should be obtained.
Copper conductors with a 95 °C isolation class should be applied.
Model
Motor
voltage
(V)
Fuse
selection (A)
FLA*
(A)
Recommended
cable size (mm²)
Cable
length
(m)
Cable size
(mm²)
Cable
length (m)
MAS 200
440
2x (3x 250)
365
2x (3x 120+70)
284
4x (3x 50+25)
147
MAS 200
480
2x (3x 250
347
2x (3x 120+70)
310
4x (3x 50+25)
160
FLA*: Full-Load Ampacity