To put the compressor back into automatic operation, select Load on the display using the
cursor keys and press the enter key.
• If the motor is stopped and automatic operation LED (7) is alight, the motor may
start automatically.
• If the week timer is active (see section
start automatically, even if it was stopped manually.
5.6
Checking the display
Warning
Before carrying out any maintenance, repair work or adjustment, stop the compressor,
press the emergency stop button and switch off the voltage.
Close the air outlet valve and open the manual condensate drain valve.
Control panel
Step
Action
1
Regularly check the display for readings and messages.
Normally, the main display is shown.
2
Always check the display and remedy the trouble if alarm LED (4) is alight or blinks.
3
The display will show a service message if a service plan interval has been exceeded or
if a service level for a monitored component has been exceeded. Carry out the service
actions of the indicated service plans or replace the component and reset the relevant
timer.
4
Regularly check the Inputs and Outputs menus for a quick look at the compressor
status.