5.7
Manual loading/unloading
Control panel
Automatic operation
Normally, the compressor runs in automatic operation, i.e. the electronic regulator loads, unloads,
stops and restarts the compressor automatically.
LED (7) is then lit.
Manual unloading
To unload the compressor manually, select Unload on display (1) using cursor keys (12) and
press enter key (10). LED (7) goes out.
Manual loading
To put the compressor back into automatic operation, select Load on the display using the cursor
keys and press the enter key. LED (7) lights up.
The Load command does not force the compressor into loaded condition, but it will switch the
compressor to automatic operation again; the compressor will be loaded if the air net pressure
drops below the programmed level.
5.8
Stopping
Important
After pressing stop button (13), the compressor will run unloaded for 30 seconds. The
compressor stops after this period. A start command during this period is ignored.
After stopping, the compressor is prevented from restarting within a programmable time
(20 seconds). A start command given during this minimum stop time will be memorized;
the automatic operation LED lights up. The compressor will start when the minimum
stop time has elapsed.
Instruction book
APF219617
65
Summary of Contents for MAS 200
Page 1: ...Instruction book APF219617 MAS 200 ...
Page 2: ......
Page 44: ...Instruction book 42 APF219617 ...
Page 49: ...Electric connections Electrical diagram Instruction book APF219617 47 ...
Page 92: ......
Page 93: ......