- 33 -
Diagnostic menu
This menu is used to power up the engine electronics
without starting the engine. When this setting is
switched on, electric power will be supplied to the
engine electronics after half a minute delay. The unit
can not be started as long as this parameter is swiched
on.
Unit menu
This menu is used to select the units into which
pressures and temperatures will be shown.
Language selection
Icons is the default factory set language, but 6 other
languages can be selected: English, French, German,
Italian, Spanish and Cyrillic (Russian). All
information in the Parameter List display is always in
English.
Engine CAN communication
This menu is used to select the type of engine
electronics, the Qc2002™ controller should
communicate with via the Canbus.
MF high frequency
This menu is used to set the maximum limit for the
mains frequency, in % of the nominal frequency (in
AMF-Auto).
MF low frequency
This menu is used to set the minimum limit for the
mains frequency, in % of the nominal frequency (in
AMF-Auto).
Diagnostics
Off Off On
Unit
C/bar C/bar F/psi
Language
English
Engine I Comm
OFF
MF high freq
100% 110 120%
MF low freq
80% 90 100%