- 50 -
Control setup
Synchronisation
2001
Type
Static sync. – Dynamic Sync.
2000 Sync. type
2141
Delay
30.0 s – 300.0 s
2142
Output A
Not Used – Option dependent
2143
Output B
Not Used – Option dependent
2144
Enable
Off – On
2145
Failclass
Alarm (1) – Trip MB (6)
2151
Output A
Not Used – Option dependent
2152
Output B
Not Used – Option dependent
2153
Failclass
Alarm (1) – Trip MB (6)
2140 MB sync failure
2150 Phase seq error
2121
Setpoint
2.0% – 20.0%
2122
Delay
0.1 s – 2.0 s
2123
Output A
Not Used – Option dependent
2124
Output B
Not Used – Option dependent
2125
Enable
Off – On
2131
Delay
30.0 s – 300.0 s
2132
Output A
Not Used – Option dependent
2133
Output B
Not Used – Option dependent
2134
Enable
Off – On
2135
Failclass
Alarm (1) – Trip MB (6)
2120 Sync. window
2130 GB sync failure
2261
Break
Close GB – Close GB+TB
2262
Delay
0.0 s – 999.0 s
2263
Rpm OK
0 rpm – 4000 rpm
2271
Delay
0.0 s – 999.0 s
2272
Output A
Not Used – Option dependent
2273
Output B
Not Used – Option dependent
2274
Enable
Off – On
2275
Failclass
Alarm (1) – Trip MB (6)
2241
GB
Not Used – Option dependent
2242
MB
Not Used – Option dependent
2251
Setpoint
0 rpm – 4000 rpm
2252
Delay
0.0 s – 999.0 s
2253
Output A
Not Used – Option dependent
2254
Enable
Off – On
2240 Sep. sync. relay
2250 Close bef. exc.
2260 Breaker seq.
2270 Cl.bef.exc.fail