- 52 -
Input/output setup
Binary input setup
Analogue input setup
3**1
Delay
0.0 s – 100.0 s
3**2
Output A
Not Used – Option dependent
3**3
Output B
Not Used – Option dependent
3**4
Enable
Off – On
3**5
Failclass
Alarm (1) – Trip MB (6)
3**6
High Alarm N/O – N/C
** = 00, 01, 02, 03, 04, 13, 14, 15, 16, 17, 18, 19, 20,
21, 22, 23, 24, 25, 43, 45, 46, 47, 48
3401
Wirebreak
Off – On
3402
Delay
0.0 s – 100.0 s
3403
Output A
Not Used – Option dependent
3404
Output B
Not Used – Option dependent
3405
Enable
Off – On
3406
Failclass
Alarm (1) – Trip MB (6)
3411
Wirebreak
Off – On
3412
Delay
0.0 s – 100.0 s
3413
Output A
Not Used – Option dependent
3414
Output B
Not Used – Option dependent
3415
Enable
Off – On
3416
Failclass
Alarm (1) – Trip MB (6)
3421
Wirebreak
Off – On
3422
Delay
0.0 s – 100.0 s
3423
Output A
Not Used – Option dependent
3424
Output B
Not Used – Option dependent
3425
Enable
Off – On
3426
Failclass
Alarm (1) – Trip MB (6)
3**0 Dig. input ***
3410 Dig. Input
3420 Dig. Input
3400 Dig. Input
* = 8, 9
41*1
Setpoint
4mA – 20mA
41*2
Delay
0.0 s – 600.0 s
41*3
Output A
Not Used – Option dependent
41*4
Output B
Not Used – Option dependent
41*5
Enable
Off – On
41*6
Fa ilclass
Alarm (1) – Trip MB (6)
41*7
High Alarm Off – On
* = 2, 3
* = 5, 6
42*1
Setpoint
4mA – 20mA
42*2
Delay
0.0 s – 600.0 s
42*3
Output A
Not Used – Option dependent
42*4
Output B
Not Used – Option dependent
42*5
Enable
Off – On
42*6
Failclass
Alarm (1) – Trip MB (6)
42*7
High Alarm Off – On
43*1
Setpoint
4mA – 20mA
43*2
Delay
0.0 s – 600.0 s
43*3
Output A
Not Used – Option dependent
43*4
Output B
Not Used – Option dependent
43*5
Enable
Off – On
43*6
Failclass
Alarm (1) – Trip MB (6)
43*7
High Alarm Off – On
41*0 4-20mA 102.*
42*0 4-20mA 105.*
43*0 4-20mA 108.*
* = 4, 5
* = 7, 8
* = 0, 1
41*1
Setpoint
0.0V DC – 40.0V DC
41*2
Delay
0.0 s – 600.0 s
41*3
Output A
Not Used – Option dependent
41*4
Output B
Not Used – Option dependent
41*5
Enable
Off – On
41*6
Failclass
Alarm (1) – Trip MB (6)
41*7
High Alarm Off – On
42*1
Setpoint
0.0V DC – 40.0V DC
42*2
Delay
0.0 s – 600.0 s
42*3
Output A
Not Used – Option dependent
42*4
Output B
Not Used – Option dependent
42*5
Enable
Off – On
42*6
Failclass
Alarm (1) – Trip MB (6)
42*7
High Alarm Off – On
44*1
Setpoint
0.0V DC – 40.0V DC
44*2
Delay
0.0 s – 600.0 s
44*3
Output A
Not Used – Option dependent
44*4
Output B
Not Used – Option dependent
44*5
Enable
Off – On
44*6
Failclass
Alarm (1) – Trip MB (6)
44*7
High Alarm Off – On
41*0 V DC 102.*
42*0 V DC 105.*
44*0 V DC 108.*