- 93 -
Rated voltage 3ph line to line
400 V
480 V
Rated voltage 3ph line to line lower voltage (optional)
230 V
-
Rated current 3ph
722 A
687 A
Rated current 3ph lower voltage (optional)
1255 A
-
Performance class (acc.ISO 8528-5:1993)
G2
G2
Single step load acceptance (0-PRP)
62%
72%
248 kW
329 kW
Frequency droop
<5%
<5%
isochronous
isochronous
Fuel consumption at 0% load
8.9 kg/h
13.2 kg/h
Fuel consumption at 50% load
42.8 kg/h
53.2 kg/h
Fuel consumption at 75% load
62.6 kg/h
73.7 kg/h
Fuel consumption at full load (100%)
82.8 kg/h
100.4 kg/h
Specific fuel consumption at full load (100%)
0.207 kg/kWh
0.219 kg/kWh
Fuel autonomy at full load with standard tank
9.4 h
7.8 h
Max. oil consumption at full load
0.10 l/h
0.11 l/h
Maximum sound power level (LWA) measured according to
2000/14/EC OND (measured at 75% PRP load)
99 dB(A)
100 dB(A)
Maximum sound power level (LPA) measured according to
Atlas Copco
-
77 dB(A)
Useful capacity of fuel tank
905 l
905 l
Single step load capability (O-PRP)
100%
100%
380 kW
457 kW
Application data
Mode of operation
PRP
PRP
Site
land use
land use
Operation
single/parallel
single/parallel
Start-up and control mode
manual/automatic
manual/automatic
Start-up time
unspecified
unspecified
Mobility/Config. acc. to ISO 8528-1:1993
transportable/D
transportable/D
Mounting
fully resilient
fully resilient
Climatic exposure
open air
open air
Status of neutral
earthed
earthed
Summary of Contents for QAS 500 Volvo S2A APP
Page 1: ...QAS 500 Volvo S2A APP Instruction Manual for AC Generators English...
Page 2: ......
Page 99: ...99 Circuit diagrams...
Page 112: ......
Page 113: ......