AP-S15HRIP / AP-S15IP / AP-S158IP
Owner’s Manual
– 32 –
AtlasIED.com
TELEPHONE: (800) 876-3333
SUPPORT@ATLASIED.COM
1601 JACK MCKAY BLVD.
ENNIS, TEXAS 75119 U.S.A.
System
Type
Networked AC Power Distribution Conditioner & Suppressor
Load Rating
Max Load 15A (1800W), Rated Load 12A (1440W)
Network Type
LAN, WEB User Interface (Note 1)
Panel
Activation Switch
Rocker with Security Bar
Circuit Breaker
15A Resettable Power Switch
Outlet On / Off Switches
Momentary Manual
AC Outlets
NEMA5-15R Switched (Programmable), Qty 8 (AP-S15HRIP Qty 5)
Note:
Outlet 8 Can Be Used to Activate a Fan Triggered by Temperature Range of On: 51° - 176°F / Off: 50° - 175°F
AC Mains IEC Power Socket
IEC NEMA 5-15P 15A 1800W with Power Cord Retainer
LAN Port
RJ45, Ethernet Port
Temp / Humidity Port
RJ14, Temperature, Humidity Probe, 2M, Probe Included
Display Port
RJ25, for AP-LEDIP Display for Voltage, Current, Temperature, Humidity, IP Address
Fault Report Port
3.5mm Jack, Fault Reporting Contact Closure, Normally Closed & Opens During Fault State, Cable Included
GPIO Fault Relay Port
Fault Relay Interface, Temperature, Humidity, Over & Under Voltage, Over Current, Surge, Cable Included
Indicators
Power On Indicator
Power Switch LED, Red
Outlet Status Indicators
Green, Qty 8 (AP-S15HRIP Qty 5)
Over Temperature Alarm Indicator
Red, Programmable Range 50° - 176°F , 10° - 80°C
Over Humidity Alarm Indicator
Red, Programmable Range 15 - 95%
Over Current / Voltage Alarm Indicator
Red, Programmable Range High - Voltage 100V - 140V, Under Voltage 80V- 120V
AC Fault Indicator
Red, Illuminates When Surge Protection is Damaged
AC Ground Indicator
Red, Illuminates When Earth Ground Is Bad
User Interface and Configuration
Web Interface
HTTP Protocol, XML Commands Available
Status
Voltage, Current, Temperature, Humidity, Spike Protection, Ground Fault, Outlet Status
Alarms
Voltage Hi / Lo, Current, System Temperature, Humidity, Fault Log
Scheduler
24 / 7, Group Schedule or Individual Outlet Schedule
Network
LAN Base, DHCP or Static IP, Individual Outlet Auto Ping Reset (Note 1)
Configuration
Outlet Renaming, Group Assignment, Sequence Delay Timing, Temperature Activated Outlet
Technical Data
Max AC Mains Current
12A, 1440W
Operating Voltage
100VAC - 132VAC
Power Consumption
8-Watts
Noise Attenuation RFI
10dB @ 10kHz / 40dB @ 100kHz / 100dB @ 10MHz
Min. Spike Clamping Voltage
460VRMS @ 3000A
Max. Spike Clamping Voltage
6000V, 1 nanosecond
Spike Clamping Voltage @ 100A
1250Vp for 20µs
Maximum Surge Current
6,500A
Energy Rating @ 2ms
600 Joules
Unit Operating Temperature Range
40º - 105ºF, 5º - 40.5ºC
Humidity Range
5% to 95% Relative Humidity
Fault Reporting
Web, GPIO Contact Closure (Closed During Normal Operation, Opens During Fault Condition), API-Commands