3.
REMOTE CONTROL (SPECIAL APPLICATION):
this special mode is
generally used to save energy in special application when -
40 °C is not really
required.
The dryer will keep the timed sequence constant but it will switch on and off
depending on the external contact connected on controller.
5.3 SET-UP
To set the dryer up, turn it on.
To enter or exit SET MENU press
button for 3 seconds.
After that the display will show first
P1
, then the default value of P1
03.
To scroll down the menu keep the button
pressed.
To change the value use
“up” and “down” buttons.
To confirm the change press
for 3 seconds. The display will show
SA
.
To set default parameters keep
“up” and “down” pressed for 3 seconds. The display
will show
dF
.
PARAMETER TABLE
Parameter
Default
Min.
Max.
STEP
UNIT
REMARKS
P1
3
1
99
1
10*s
Value of repress ration, shown in tens of seconds.
Example 3=30 seconds
P2
24
6
36
1
10*s
Value of drying and purge, shown in tens of seconds.
Example 24=240 seconds
P3
-39
-80
+20
1
°C
SETPOINT value; the minus sign is shown by the
lowest decimal point blinking (39. means -39)
P4
0
0
3
1
CONTROL MODE; selects the CONTROL MODE
during OPERATING MODE.
Summary of Contents for HGL 120
Page 17: ...B Schemat przep ywu powietrza...
Page 18: ...C Wymiary osuszacza...
Page 20: ...D Schemat elektryczny...
Page 21: ...E Widok rozstrzelony...
Page 23: ...DESICCANT DRYER Instruction and Maintenance Manual...
Page 24: ...HGO 40 160 HGL 40 160...
Page 27: ...B Flow diagram C Dryer dimensions D Wiring diagram E Exploded view F Suggested spares...
Page 41: ...LIST OF ATTACHMENTS...
Page 44: ...A C IN L E T O U T L E T IN L E T E B F G D MODEL 40 80 120 160 INLET OUTLET INLET...
Page 46: ...D WIRING DIAGRAM C CONTROLLER EMV 1 EMV 2 EMV 3 EMV 4 EMV ELECTROMAGNETIC VALVE...