background image

6

trouBLESHooting

Most problems are easily remedied by consulting the trouble-
shooting guide. If problems still persist, contact Atwood or an 
authorized service center. Only a qualified technician should do 
any work involving the gas system.
A periodic visual check of the burner flames should be done 
by observing the flame through the “peep hole” in the heat 
exchanger. There should be blue flame with minimum or no 
yellow tipping.
Burner maintenance should be performed by an Atwood 
Authorized Service Technician.

NOTE:

 The heater is dormant until it senses water 

flow. When a water tap is turned on to at least .5 GPm 
the burner will fire until water flow is turned off and 
the heater again goes dormant.

Heater Does not come on When The Water is turned 
on. (Power vent not running)

1.  Locate the ECO, high temperature switch (two red wires)  
 

at the upper left hand of the heat exchanger. Check for   

 

open circuit condition. The ECO should be reset by  

 

 

pushing the reset button when temperature drops below  

 

160 degrees.

2.  Be sure all electrical connectors are secure and the  

 

 

polarity is correct. (Red wire to positive terminal).

3.   Be sure power is on and panel breaker is not tripped.
4.   Check electrical contacts. Be sure the connector is  

 

 

plugged into board. Using a voltmeter, check for 12 Volts  

 

on this connector.

5.   Fuse in power wire might be blown. Replace fuse.
6.   Be sure there is a battery in the system. never connect   
 

the heater directly to a power converter. Some converters  

 

have circuits that are not pure DC. This can cause  

 

 

malfunctions or damage to the heater and is not covered  

 

by warranty.

7.   Be sure that no water-mixing valve has been left in the on  
 

position, using the showerhead as a shut off. This will    

 

permit water to bypass the water heater and bleed cold   

 

water into the hot water system. Always turn off both hot  

 

and cold water valves after using.

8.   Be sure that the bypass valve at the water plumbing  

 

 

connections is in the “off” position. An open valve can    

 

also permit water to bypass heater, causing it not to fire.

There is no ignition When Water is on (Power vent is 
running)

1.   Be sure the gas valve at the tank is “On”, there is gas in  
 

the tank and the gas line is purged of all air.

2.   Be sure that water flow is at least 0.5 gallon/minute.
3.   Check that the ignition wire is plugged into the spark    
 

tower on the ignition control and is not touching anything  

 

else.

4.   Check flame site hole to see if igniter is sparking from the  
 

probe to the burner. Bend ignition wire to adjust to proper  

 

gap or contact Atwood or you’re nearest authorized  

 

 

service representative.

5.  Check that there are no cuts or breaks in the wire. Align it  

 

so that it is not in contact with anything but the terminal.

6.  Be sure that the power vent fan has 12 volts to it when    
 

there is water flowing and there are no obstructions in the  

 

flue pipe.

7.   Safety pressure switch may be out of adjustment. Contact  
 

Atwood or your nearest authorized service representative.

no Water flows from Tap When Tap is Turned on.

1.  Be sure that water supply is turned on and that there are  
 

no obstructions.

2.   Hot and cold water lines connected to heater are  

 

 

reversed. Correct by reversing their positions.

burner Turns on but Temperature fluctuates 
erratically.

1.  May be caused by excessive restriction at the water  

 

 

outlets, showerheads, aerators or water strainers. These  

 

should be cleaned and any showerhead flow restrictor    

 

removed.

2.  The gas modulating valve is out of calibration. Consult    
 

Atwood.

Heater comes on but rapidly cycles on and off.

1.  Water flow is too low. Increase flow at a tap. Clean all    
 

aerators and shower head screens to assure at least .5    

 

GPM of water flow

2.   Water pump is not functioning properly. Repair or replace  
 

pump.

3.   If the heater cycles as the pump cycles, a pressure  

 

 

accumulator tank is needed in the water system. If you    

 

have an accumulator tank, check to see if it has become  

 

filled with water. If it has, drain it so that it contains air    

 

only.

4.   Air is in the water line. Bleed air by turning on all water    
 

taps.

burner ignites but Water Temperature is Too low

1.  The water flow may be so high as to exceed the capacity  
 

of the heater particularly if your supply water is very cold.  

 

Slow the water flow.

2.   The gas pressure may be too low. Be sure the gas flow   
 

control valve is in full “on” position.

3.   Check the gas pressure while the water is on at full flow.  
 

The LPG pressure should be the “manifold pressure” as  

 

shown on the specification label while the heater is  

 

 

running. A gas-testing gauge should be installed on the   

 

manifold tap so that it may be read while heater is  

 

 

running. If it is too low, turn up the gas regulator to the    

 

proper pressure. This should only be done by a qualified  

 

technician.

4.   The gas flow may be too low due to improper gas line    
 

diameter (under 3/8 inch outside diameter). The gas line   

 

may be excessively long (over 20-30 feet) or the on/off    

 

solenoid at the tank (if you have one) may have an orifice  

 

that is too small (under 3/16th of an inch).

5.   Check the heater door louvers and flue pipe for airflow    
 

obstructions and clean.

Summary of Contents for MPD 90222

Page 1: ...Input in 1000 s Btu 01__________ Generation m critical installation warnings Install in recreation vehicles only RV s are recreation vehicles designed as temporary living quarters for recreation camping or travel use having their own power or towed by another vehicle All combustion air must be supplied from outside the RV and all products of combustion must be vented to outside the RV DO NOT vent ...

Page 2: ...ior to erecting the walls NOTE Parts bagged and included with the unit include corner filler brackets flue screen and cover hole bushing 1 Locate the water heater on the floor of the coach at pre determined location The unit must be permanently supported at the same level as the bottom of the sidewall cutout by the floor or a raised floor 2 To install the unit on carpeting assure the addition of m...

Page 3: ...MP 12 VDC GAS ORANGE FROM W H 9 Place flue screen from parts bag over end of flue tube Place the access door on the lower flange pins aligning the holes in the bottom of the door Carefully close the top edge of the door being careful to align the flue opening with the flue tube and screw in the fastener Push snap plastic bushing supplied in parts bag into the hole in the door front 10 The applianc...

Page 4: ...ARK SENSE WIRING SCHEMATIC GREEN GREEN RED RED PURPLE BROWN BROWN RED RED RED PURPLE RED RED BLUE BLUE LOCKOUT LAMP OPTIONAL MPD 90211 m CAUTION FIRE DO NOT smoke of have any flame near an open faucet GENERAL INFORMATION LP and Water system must be turned on Have gas pressure tested periodically Should be set at 11 inches of water column with three appliances running Drain water heater at regular ...

Page 5: ...0 Gas Inlet Tube 90273 11 Ignition Control 90274 12 Flue Outlet Screen 90275 13 Flue Tube 90276 14 Pressure Switch 90277 15 Blower Assembly 90278 16 Fan Base 90279 17 Flue Hood Assembly 90280 18 Case Assembly 90281 19 Heat Exchanger 90282 20 ECO 90283 21 Plug 90284 ITEM DESCRIPTION PART 22 Orifice 72 45 000 Btu 90285 23 Orifice 71 50 000 Btu 90286 24 Orifice 0 27 55K for PT 3392 Inquire 25 Pressur...

Page 6: ...is sparking from the probe to the burner Bend ignition wire to adjust to proper gap or contact Atwood or you re nearest authorized service representative 5 Check that there are no cuts or breaks in the wire Align it so that it is not in contact with anything but the terminal 6 Be sure that the power vent fan has 12 volts to it when there is water flowing and there are no obstructions in the flue p...

Page 7: ...art defective in material or workmanship This warranty includes reasonable labor charges required to remove and replace the part Service calls to customer s location are not considered part of these charges and are therefore the responsibility of the owner 3 This warranty does not cover the following items classified as normal maintenance a adjustment of gas pressure b cleaning or replacement of b...

Page 8: ...8 intentionally left blank ...

Page 9: ...ou les fuites n ont pas été réparées L installation et la réparation doivent être effectuées par un installateur qualifié une agence de service ou le fournisseur de gaz Explication du numéro du modèle OD_____________________ À la demande On demand 45________________ Entrée en milliers de BTU 01__________ Génération m AVERTISSEMENTS CRITIQUEs SUR L INSTALLATION À installer dans les véhicules récréa...

Page 10: ...ompte ou le service à la clientèle Atwood Avant de commencer assurez vous que l emplacement approprié a été déterminé et installé par le FEO avant l érection des murs REMARQUE Les pièces ensachées et venant avec l unité de remplissage comprennent le support de fixation la grille du conduit d air et la douille du trou de couverture 1 Localisez le chauffe eau sur le plancher du véhicule à l emplacem...

Page 11: ...alve doit avoir un réglage de la pression maximale qui ne doit pas dépasser 100 lb po Installez le remplacement de la valve dans l orifice prévu et désigné à cet effet sur le chauffe eau Adaptateur Installation dans l ouverture d un chauffe eau de 10 gallons standard avec la trousse et l adaptateur pour une grande porte 7 Pour prévenir les fuites d eau calfeutrez soigneusement le pourtour arrière ...

Page 12: ...ndre le chauffe eau couper l eau 7 En cas de surchauffe ou si l approvisionnement en gaz ne s arrête pas fermer l interrupteur On Off ROUGE est le courant positif d entrée de 12 V c c VERT est la mise à la terre de 12 V c c BLEU est le signal de verrouillage de 12 V c c positif Voir l illustration de la configuration de commutation type BLEU DU CHAUFFE EAU LAMPE DE VERROUILLAGE 12 V c c GAZ ORANGE...

Page 13: ...igé remplacer le fusible de 2 ampères par un mini fusible ATO Ne pas installer un fusible de plus de 3 ampères Si le fusible est bon et que l unité ne fonctionne pas vérifier si l appareil ne présente pas une tension excessive plus de 14 volts Fonctionnement hivernal et hivernage du chauffe eau Il n est pas recommandé d utiliser les systèmes d eau pendant l hiver Tout gel du chauffe eau ou des aut...

Page 14: ...e d allumage 90274 12 Grille du conduit d air 90275 13 Tube d appel d air 90276 14 Pressostat 90277 15 Ens ventilateur 90278 16 Base ventilateur 90279 17 Ens hotte du conduit d air 90280 18 Ens du boîtier 90281 19 Échangeur de chaleur 90282 20 ECO 90283 21 Fiche 90284 ARTICLE DESCRIPTION Nº DE PIÈCE 22 Orifice nº 72 45 000 BTU 90285 23 Orifice nº 71 50 000 BTU 90286 24 Orifice 0 27 55K pour PT nº ...

Page 15: ...e qui évitera son déclenchement Il n y a pas d allumage lorsque l eau est activée le ventilateur est en marche 1 Assurez vous que la soupape de gaz du réservoir est à On qu il y a du gaz dans le réservoir et que la conduite de gaz est complètement purgée d air 2 Assurez vous que le débit d eau est d au moins de 0 5 gal minute 3 Vérifiez si le câble d allumage est branché dans la tour d allumage su...

Page 16: ...clusions précédentes ne s appliquent pas à vous 10 Les garanties implicites se limitent à une période de deux 2 ans Certains États n autorisent pas les restrictions sur la durée d une garantie implicite par conséquent il est possible que les restrictions précédentes ne s appliquent pas à vous Cette garantie vous accorde des droits légaux spécifiques et vous pouvez aussi avoir d autres droits pouva...

Page 17: ...r cooler hot water temperatures the modulating valve can be adjusted clockwise toward the MIN position One should use caution not to force the valve adjustment beyond the MAX and MIN points Some factors relating to output performance are 1 City or Park Water Service incoming pressures 2 Obstructions or restrictions in the water system including water bypass valves in vehicles The bypass valve in y...

Reviews: