background image

TH146-P-U 

                                              2/8

1) Choose a location about 1.5 m (5 ft) above the floor on an 

inside wall.

2) Loosen the captive screw under the console.
3) Detach the console from its base by pulling the bottom section.
4) Secure the base using the wall anchors and screws.
5) Connect the console to controller terminals TH and TH (no 

polarity).

The terminals used to connect the heating/cooling system depend 
on the type of system. See the appropriate wiring table on page 4.

If you have an add-on installation, you may need an RC845 relay to 
connect the furnace (auxiliary heat) and its fan to the controller. 
Install the relay near the control module and connect the wires as 
follows:

• relay terminals W, G and C to controller terminals W1, G and 

C. 

• relay terminals T and T to the appropriate furnace terminals: 

T and T (oil); TH and TH (gas); R and W (electric).

NOTE: Refer to the relay’s installation instructions for more details.

If you have a 3H1C or 4H2C heat pump, a second RC845 relay 
might be required to connect the second auxiliary heat.

Connect the humidifier in series with the power supply between 
controller terminals H and H (dry contact).

Connect the dehumidifier or air exchanger in series with the power 
supply between controller terminals D and D (dry contact).

The outdoor sensor is required for the following:

• outdoor temperature display
• balance points (heat pumps only, see section 4.2)
• defrost point (heat pumps only, see section 4.3)
• automatic humidity control (see user guide)
• use of an air exchanger (see section 4.10)

When installing the sensor, observe the following guidelines:

• Avoid locations where the sensor can be covered with snow 

or exposed to direct sunlight. 

• Avoid air outlets and concealed chimneys or stove pipes.

Install the sensor using its mounting clip and connect it to controller 
terminals OS and CS (no polarity).

NOTE: The maximum wiring length is 30 m (100 ft).

The plenum sensor is required for the following:

• low temperature limit inside the plenum (HVAC only)
• high temperature limit inside the plenum (HVAC only)
• fan limit if gas heating is used (HVAC only)
• high pressure protection during defrost cycle (This protection 

is generally needed for add-on installations only. It is not 
needed if the heat pump is not connected to the controller 
terminal WW.)

Install the sensor on the side of the plenum and 
position it such that its aperture faces the air 
flow.

Connect the sensor to controller terminals PS 
and CS (no polarity). For more information, 
refer to the instructions provided with the 
sensor.

NOTE: The maximum wiring length is 30 m (100 ft).

NOTE: The dual-energy input can be used only with a heat pump 

equipped with auxiliary heat.

The dual-energy input can be connected to the dual-register meter 
equipped with a normally open (NO) dry contact. Connect the 
controller terminals DE and CC to the meter terminals (yellow and 
red wires). 
The contact closes when the outdoor temperature drops below the 
temperature setting on the meter. When the contact is closed, the 
heat pump is disabled and only the auxiliary heat can be used.

To use the unoccupied mode, the controller requires a remote 
control device such as Aube’s CT241 telephone controller equipped 
with a normally open (NO) dry contact placed between terminals 
UN and CC of the controller. The unoccupied mode is activated 
when the contact closes. (See user guide.)

To access the configuration switches, loosen the captive screw 
under the console and pull the console from its base.

Access Mode (SW1-1)

INST: Installer mode. Gives access to all configuration 
parameters.

NOTE: In installer mode, the short-cycle protection is disabled 
and the interstage delay is reduced to 1 minute.

USER: User mode. Gives access to configuration parameters 1 
to 4 only (see page 8).

Keypad Lock (SW1-2)

I: The keypad is locked. Settings cannot be changed.
O: The keypad is unlocked.

1) Place the console in Installer mode (INST) using the SW1-1 

switch on the back of the console.

2) Press the Mode button for 3 seconds to access the 

configuration menu (see page 8). The first menu item 
(parameter) is displayed.

3) To view another menu item, briefly press the Mode button.
4) To modify a parameter, press either 

 button.

5) To exit the configuration menu, press  .
6) Return the console to User mode (USER).

2.3

 Heating/Cooling System

2.4

RC845 Relay

2.5

 Humidifier

2.6

 Dehumidifier / Air Exchanger

2.7

Outdoor Sensor (AC144-03)

2.8

 Plenum Sensor (AC146-410)

2.9

 Dual-energy Input

2.10

 Unoccupied Mode Input

3. Configuration

3.1

 Configuration Switches

3.2

 Configuration Menu

Summary of Contents for CT280-3H3C

Page 1: ...ule Install the control module near the heating cooling system away from any heat source Install the console in a central location Avoid locations with air drafts e g top of staircase or air outlet or...

Page 2: ...ed for add on installations only It is not needed if the heat pump is not connected to the controller terminal WW Install the sensor on the side of the plenum and position it such that its aperture fa...

Page 3: ...nace the auxiliary heat source is installed at the same time as the heat pump In this type of installation the indoor coils are located upstream of the auxiliary heat When the controller is configured...

Page 4: ...ry heat 2 24 Vac 1 A W3 O B Reversing valve 24 Vac 1 A G Fan 24 Vac 1A L Fault 24 Vac 5 mA WW Defrost 24 Vac 5 mA NOTE Requires a dry contact do not connect to a solid state relay such as a triac NC N...

Page 5: ...TH146 P U 5 8 Wiring Diagram 2H1C Heat Pump New Installation AC146 410 AC144 03 CT241 Humidifier Dehumidifier Compressor Auxiliary Heat Reversing Valve Fan Fault Defrost Dual Energy...

Page 6: ...TH146 P U 6 8 Wiring Diagram 3H2C Heat Pump Add on Installation AC146 410 AC144 03 CT241 Fault Defrost Reversing Valve Compressor 1 Compressor 2 Furnace Fan Limit Humidifier Dehumidifier Dual Energy...

Page 7: ...TH146 P U 7 8 Wiring Diagram 3H2C HVAC AC146 410 AC144 03 CT241 Cooling Unit 1 Cooling Unit 2 Heating Unit 1 Heating Unit 2 Fan Heating Unit 3 Humidifier Dehumidifier...

Page 8: ...on 4 6 NOTE The function is disabled if HLMT is set above its maximum 12 Cycles per hour 4 2 to 6 Select the number of heating cooling cycles per hour For optimal heating control use the setting that...

Page 9: ...ule Installer le module de contr le pr s du syst me de chauffage et climatisation loin des sources de chaleur Installer la console un endroit central viter les endroits o il y a des courants d air ex...

Page 10: ...u pl num et la positionner de sorte que l ouverture de lecture soit face au courant d air Raccorder la sonde aux bornes PS et CS du contr leur aucune polarit Pour plus d information se r f rer aux ins...

Page 11: ...mont du chauffage d appoint Lorsque le contr leur est configur pour une nouvelle installation la thermopompe et le chauffage d appoint peuvent fonctionner en m me temps Le d lai d activation est le te...

Page 12: ...ca 1 A W3 O B Valve d inversion 24 Vca 1 A G Ventilateur soufflerie 24 Vca 1A L D faut 24 Vca 5 mA WW D givrage 24 Vca 5 mA NOTA Exige un contact sec ne pas relier un relais semi conducteur tel un tri...

Page 13: ...8 Sch ma de branchement thermopompe 2H1C nouvelle installation Compresseur Valve d inversion Ventilateur D faut D givrage Chauffage d appoint AC146 410 AC144 03 Humidificateur D shumidificateur CT241...

Page 14: ...hement thermopompe 3H2C installation add on installation modifi e Fournaise Thermostat ventilateur D faut D givrage Valve d inversion Compresseur 1 Compresseur 2 AC146 410 AC144 03 Humidificateur D sh...

Page 15: ...TH146 P U 7 8 Sch ma de branchement CVAC 3H2C Refroidissement 1 Chauffage 1 Chauffage 2 Ventilateur Chauffage 3 AC146 410 AC144 03 Humidificateur D shumidificateur CT241 Refroidissement 2...

Page 16: ...ctiv e lorsque HLMT est plac au dessus du maximum 12 Cycles par heure 4 2 6 Permet de s lectionner le nombre de cycles par heure Pour un contr le optimal du chauffage choisir le r glage qui correspond...

Reviews: