AUBER INSTRUMENTS
WWW.AUBERINS.COM
2017.10 P1/4
ECT-100 Temperature Controller
Version 1.4 (Oct, 2017)
1. Overview
This is an economical plug-n-play controller that can be used for Sous Vide
cooking, and other low temperature control applications (<221° F or 105° C). It
offers PID mode for heating control, as well as on/off control mode for either
heating or cooling. The PID mode is suitable for precision temperature control
such as Sous Vide cooking. The on/off control is suited for controlling devices
that does not like to be switched on/off too frequently such as the compressor
of the refrigerator.
This controller has a temperature sensor comes with it, which can measure
temperature in the range of -50 ~ 120° C (-58 ~ 248° F). The power input can be
either 120V AC or 240V AC. The output power will be supplied to the output
socket, to which a load can be plugged. The output power is controlled by an
internal electromechanical relay whose action synchronize with the OUT
indicator on the front panel. The output voltage is the same as the input voltage.
2. Specification
Temperature control range
-50 ~ 105° C, -58 ~ 221° F
Temperature resolution
1° C (between -50 ~ 120° C)
1° F (between -58 ~ 248° F)
Temperature accuracy
0.5 ° C or 0.9 ° F
Control mode
On/off (heating or cooling), PID (heating)
Control output
12A at 120VAC, 10A at 240VAC
Operating input voltage
85 ~ 240V AC, 50/60Hz
Audio Alarm
High and low limit
Sensor type
Silicon band gap sensor
Sensor size
0.25” OD (6.35 mm) x 1"
length (25 mm)
Sensor connection
3-pin connector
Sensor cable length
6 ft (2 m)
Dimension
3.4
’’
x1.7
’’
x 4.7
’’
(85 x 47 x 118 mm)
Ambient temperature
-20 ~ 50° C (0° F ~ 120° F)
Power cable length
3 ft (1 m)
Warranty
One (1) year
3. Front Panel and Connectors
①
②
③
④
⑤
Figure 1. Front Panel.
⑥
⑦
⑧
Figure 2. Bottom Panel
①
Set Key
②
Down Key
③
Up Key/Mute
④
Output Indicator
⑤
Temperature Display
⑥
Power Output Socket
⑦
Power Input
⑧
Sensor Input
4. Temperature Setup
To change its preset temperature: Press SET key once to switch the display
from actual temperature to set temperature. The display will start to blink.
Press Up and Down keys to increase or decrease the setting temperature.
When finished, press SET key once to confirm and exit.
Note:
Parameter remains unchanged unless you press set key to confirm.
5. Parameter Setup
To enter parameter setting mode, press and hold SET key for 6s and it will
show
“AH” in the display
window. Please see Table 1 for all parameters.
Please refer to the flow chart in Figure 1 for how to change parameters.
Table 1. Parameter Settings and its initials.
Symbol
Display
Description
Range
Initial
AH
AH
High Limit Alarm
-99-999
210
AL
AL
Low Limit Alarm
-99-999
32
Mod
MND
Control mode
PID
HEA (heating)
COL (cooling)
PID
AS
AS
Anti-short cycle delay
(only valid for cooling mode)
0-200
6
Hy
Hy
Hysteresis band
0-999
3
P
p
Proportional band (in 1 degree)
0-999
18
I
I
Integral constant (second)
0-999
650
d
d
Derivative constant (second)
0-999
40
t
T
Cycle rate (second)
0-999
20
AT
AT
Auto-tune
0=off, 1=on
0
C-F
C-F
Temperature unit
° C or ° F
° F
oFS
Ofs
Input offset
-99-99
0
Instruction Manual