background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2017.10                                                                     

   

                                                       P2/3 

 

Details about each parameter 

 

AH

. High limit alarm. When process temperature is higher than AH, the 

internal audio buzzer will be energized. For example, if AH set to 290, the 
buzzer  will  be  on  at  291  and  off  at  290.  When  the  buzzer  is  on,  the 
display  window  will  be  flashing  between 

A-H

  and  the  current  process 

temperature. Press Up key to mute the alarm. 

 

AL

.

 

Low  limit  alarm.  When  process  temperature  is  lower  than  AL,  the 

internal audio buzzer will be energized. For example, if AL is set to 100. 
The buzzer will be on when temperature drop to 99. It will be turned off 
when temperature rise above 100. The low limit alarm is suppressed at 
powering up. It will be reactivated once the temperature has reached set 
point. When the buzzer is on, the display window will be flashing between 

A-L

 and the current temperature. Press Up key to mute the alarm.

 

 

Mod

.

 

Control mode. Three control modes are available: 

PID

 (PID mode 

for  heating), 

HEA

  (on/off  mode  for  heating),  and 

COL

  (on/off  mode  for 

cooling).

  

 

AS

.

 

Anti-short cycle delay. This is the delay time to turn on the cooler 

(e.g., refrigerator). If the cooler is compressor based, compressor should 
not be turned on immediately when it is at high pressure (just after turned 
off). Otherwise, it may shorten the life of compressor. The anti-short cycle 
delay function can be used to prevent the rapid cycling of the compressor. 
It establishes the minimum time that the compressor remains off (after 
reaching

 

cutout) before turns on again. The delay

 

overrides any controller 

demand and does not allow the compressor to turn on until the set delay-
time has elapsed. It gives time to release the refrigerant pressure through 
evaporator. It typically set to 6 (minutes). The unit is in minutes. This 
setting is only valid for cooling mode.

  

 

Hy. 

Hysteresis  band  (or  dead  band).  This  parameter  is  valid  only  for 

on/off control mode (heating or cooling). In the on/off heating mode, the 
controller  will  stop  sending  power  to  the  heater  when  temperature  T  is 
above the set value (SV), and start sending power again to the heater if T 
drops below  (SV-Hy). For example,  if SV=100 ° C. Hy=3 ° C, the heater 
will  be  turned  off  when  the  temperature  rises  above  100  ° C;  it  will  be 
turned  on  again  as  the  temperature  drops  below  97  ° C.  For  the  on/off 
cooling  mode,  the  compressor  will  be  turned  off  when  T<SV.  It  will  be 
turned on again when T>SV+Hy.

 

 

P

.

 

Proportional band. The unit is 1 degree. This parameter controls the 

output  level  based  on  the  difference  between  the  process  temperature 
and set temperature. The greater P value, the weaker the action  (lower 
gain).  If  P=7,  the  proportional  band  is  7  degree.  When  the  sensor 
temperature is 7 degrees below the proportional band (10 degrees below 
the setting), the controller will have 100% output. When the temperature 
is 5 degree below the set point, the output is 71%. When the temperature 
is  equal  to  the  setting,  the  controller  will  have  0%  output  (assuming 
integral and derivative functions are turned off). This constant also affects 
both integral and derivative action.  Smaller P values will make the both 
integral and derivative action stronger. Please note the value of the P is 
temperature  unit  sensitive.  If  you  found  an  optimized  P  value  when 
operating  the  controller  in  Fahrenheit,  you  need  to  divide  the  P  by  1.8 
when changing the temperature unit to Celsius. 

 

I

.

 

Integral time. The unit is in seconds. This parameter controls the output 

of  controller  based  on  the  difference  between  the  measured  and  set 
temperature  integrated  with  time.  Integral  action  is  used  to  eliminate 
temperature offset. Larger number means slower action. e. g. assuming 
the difference between the measured and set temperature is 2 degrees 
and  remain  unchanged,  the  output  will  increase  continuously  with  time 
until  it  reaches  100%.  When  temperature  fluctuate  regularly  (system 
oscillating),  increase  the  integral  time.  Decrease  it  if  the  controller  is 
taking too long to eliminate the temperature offset. When I=0, the system 
becomes a PD controller. For very  slow response system such as slow 
cooker and large commercial rice cooker, set I = 0 will significantly reduce 
the temperature overshoot. 

 

d

. Derivative time. The unit is in seconds. Derivative action contributes 

the output power based on the rate of temperature change. Derivative 
action can be used to minimize the temperature overshoot by responding 
its rate of change. The larger the number is, the faster the action will be. 

For example, when there is a disturbance causing the temperature 
dropping at a very high rate, the derivative action can change the 
controller output based on the rate of change rather than the net amount 
of change. This will allow the controller to act sooner. It will turn the 
heater to full power before the temperature drops too much. 

 

t

.

 

Cycle rate. The unit is in seconds. This unit determines how long for the 

controller to calculate each action. For example, if T is set to 20 seconds, 
when the controller decides the output should be 10%, it will turn on the 
heater 2 second for every 20 seconds. This parameter should set at 20 
seconds for the internal mechanical relay. This setting is also 
recommended for controlling a solenoid valve or a compressor of 
refrigerator to reduce the frequency of on/off. 

 
 
 

Push down 

for 6s

74

ah

200

SET

SET

SET

^

V

al

20

SET

SET

V

^

mod

P

/

d

SET

SET

^

V

as

6

SET

SET

V

^

hy

3

SET

SET

^

V

p

18

SET

SET

V

^

i

645

SET

SET

^

V

d

40

SET

SET

V

^

t

20

SET

SET

^

V

at

0

SET

SET

V

^

C-f

O

F

SET

SET

^

V

ofs

0

SET

SET

V

^

end

SET

 

Figure 1. Flow chart of setting up parameters. 

 

Reviews: