AUBER INSTRUMENTS
WWW.AUBERINS.COM
2017.01 P1/5
SYL-2813A Dual-Input Automotive Multimeter
Version 1.6 (Mar, 2019)
A. Specifications
Table 1. Specifications of SYL-2813A Automotive Multimeter.
Power Supply
DC 12 -30 V (Isolated)
Power Consumption
< 2 Watt
Relay Contact Rating
3 A at 220 VAC
Input Type
Thermocouple
: K, E, S, R, J, T, B, WRe3/25.
Resistance
: Pt100, Cu50, (375R)*
Voltage
: 75 mV, 30 mV, 0 - 5V, 1 - 5V, 10 V
Amperage
: (0 - 10 mA, 0 - 20 mA, 4 - 20 mA)*
Input Channels
Channel 1, Channel 2
Display Range
-1999 ~ 9999
Accuracy
± 0.2% of full input range or ± 1 unit
LED Display
0.48’’ red/green color
Outside Dimension
48 x 48 x 75 mm (1/16 DIN)
Mounting Cutout
45 x 45 mm
Working Condition
-20 ~ 50
˚
C, 85% RH
Note
: * input types that are in parenthesis are only available to channel 1, these input
types are not available to channel 2.
B. Front Panel
⑨
⑩
⑧
⑦
⑥
③
④
②
①
⑤
Figure 1. Front panel of SYL-2813.
①
Alarm1 and relay J1 indicator (red LED)
②
Alarm2 and relay J2 indicator (red LED)
③
Maximum value indicator of Channel1 (red LED)
④
Maximum value indicator of Channel2 (red LED)
⑤
SET key
⑥
SHIFT key
⑦
DOWN key
⑧
UP key
⑨
Display1 window (top display)
⑩
Display2 window (bottom display)
1. AL1 (or AL2) on indicates alarm is on and J1 (or J2) relay is pulled in
(closed).
2. PK1 (or PK2) is on when display windows shows the maximum value MA1
of Channel 1 (or the MA2 of Channel 2) and the time MAt1 (or MAt2) when the
peak value was caught.
3. SET key. In Normal Operating Mode, press SET once, enter the code for a
setting mode. Press SET again to enter the setting mode. In Parameter Setting
Mode, press it to select a parameter or to save the value.
4. SHIFT key “>”. In the Parameter Setting Mode, press this key to select the
digit to be changed. In the Normal Operating Mode, press this key to toggle the
displayed variables between Process Values (PV1 and PV2), Maximum Value
of Channel 1 (MA1 and MAt1), and Maximum Value of Channel 2 (MA2 and
MAt2). See the diagram below. Please note that time is expressed in seconds
when it is less than 9999 seconds. Time longer than 9999 seconds will be
displayed as Hours. Minutes (hh.mm).
5. DOWN key “V”. In the Parameter Setting Mode, press it to scroll the
parameter list in a reversed order or decrease the parameter value. In the Peak
Value Checking Mode, press it for 2 seconds to reset the peak values stored in
the memory. In the Normal Operating Mode, press this key to toggle the
display the current readout and value difference if the feature is enabled.
6. UP key “
Λ
”. In the Parameter Setting Mode, press it to scroll the parameter
list or to increase the parameter value. In the Normal Operating Mode, press
this key to toggle the display brightness between bright and dim. Each time the
key is pressed the display brightness will be changed.
PV2
PV1
MAt1
MA1
MAt2
MA2
Process Values
(PK1 and PK2 are off)
Peak Value of
Channel 1
(PK1 on)
Peak Value
of Channel 2
(PK2 on)
“>” Key
“>” Key
“>” Key
Figure 2. Diagram of how to check Peak Values.
C. Terminal Assignments
6
7
8
9
10
14
13
12
11
1
2
3
4
5
SYL-2813
J1 output
(NO)
J2 output
(NO)
DC 12V
Gnd
TC1
mA1
mV1
TC2
mV2
RTD1
RTD2
P2 (V2)
P1 (V1)
Light
Int.
5V out
COM
(J1/J2)
+
−
Figure 3. Terminal assignments of SYL-2813.
Instruction Manual