SPECIFICATIONS
Page 10
MVS User Manual
710-13019-00A
Control Inputs
Start (Terminals C23, C24) ................................................................................................................................................. 24 VDC, 8 mA approx
Stop (Terminals C31, C32) ................................................................................................................................................. 24 VDC, 8 mA approx
Reset (Terminals C41, C42) ............................................................................................................................................... 24 VDC, 8 mA approx
Input A (Terminals C53, C54) .......................................................................................................................................... 24 VDC, 8 mA approx
Input B (Terminals C63, C64) ........................................................................................................................................... 24 VDC, 8 mA approx
Motor Thermistor (Terminals B4, B5) ..................................................................................................................................... Trip point > 2.4 k
NOTE
All control inputs are potential free. Do not apply external voltage to these inputs.
Low Voltage Supply
Rated Voltage ...................................................................................................................................................................... 110 ~130 or 220 ~ 240 V
Rated Frequency ..................................................................................................................................................................................................... 50/60 Hz
Typical power consumption ....................................................................................................................................................... 70 W
3
continuous
Outputs
Relay Outputs ..................................................................................................................................................................... 10 A @ 250 VAC resistive
.............................................................................................................................................................................................. 6 A @ 250 VAC 15 p.f. 0.3
................................................................................................................................................................................................. 10 A @ 30 VDC resistive
Outputs on interface PCB
Main Contactor (13, 14) ............................................................................................................................................................ Normally Open
Bypass Contactor (23, 24) ........................................................................................................................................................ Normally Open
Run Output/ PFC (33, 34) ........................................................................................................................................................ Normally Open
Outputs on Controller
Output Relay A (43, 44) ............................................................................................................................................................ Normally Open
Output Relay B (51, 52, 54) .......................................................................................................................................................... Changeover
Output Relay C (61, 62, 64) ............................................................................................................................................................ Changeover
Analog Output (B10, B11) ..................................................................................................................................................... 0-20 mA or 4-20 mA
Environmental
Degree of Protection
Power
Assembly
...................................................................................................................................................................................................... IP00
Controller .......................................................................................................................................................................................... IP54/ NEMA 12
Operating Temperature ..................................................................................................... - 10
˚
C to + 60
˚
C, above 40
˚
C with derating
Storage Temperature ..................................................................................................................................................................... - 25
˚
C to + 80
˚
C
Humidity ........................................................................................................................................................................ 5% to 95% Relative Humidity
Pollution Degree ................................................................................................................................................................................ Pollution Degree 3
Vibration ........................................................................................................................................................................................ Designed to IEC 60068
EMC Emission
Equipment Class (EMC) .......................................................................................................................................................................................... Class A
Conducted Radio Frequency Emission ....................................................................................... 10 kHz to 150 kHz: < 120 - 69 dB µV
............................................................................................................................................................................ 0.15 MHz to 0.5 MHz: < 79 dB µV
................................................................................................................................................................................ 0.5 MHz to 30 MHz: < 73 dB µV
Radiated Radio Frequency Emission ....................................................................................... 0.15 MHz to 30 MHz: < 80-50 dB µV/m
................................................................................................................................................................. 30 MHz to 100 MHz: < 60-54 dB µV/m
.................................................................................................................................................................. 100 MHz to 2000 MHz: < 54 dB µV/m
This product has been designed as Class A equipment. Use of this product in domestic environments may cause radio interference,
in which case the user may be required to employ additional mitigation methods.
EMC Immunity
Electrostatic Discharge .................................................................................................................. 6 kV contact discharge, 8 kV air discharge
Radio Frequency Electromagnetic Field ..................................................................................................... 80 MHz to 1000 MHz: 10 V/m
Fast Transients 5/50 ns (main and control circuits) .......................................................................... 2 kV line to earth, 1 kV line to line
Surges 1.2/50 µs (main and control circuits) .................................................................................. 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption (safe shutdown) .......................................................... 5000 ms (at 0% nominal voltage)
Standards Approvals
C
....................................................................................................................................................................................................... EMC requirements
CE .......................................................................................................................................................................................................... EMC EU Directive
1
Short circuit current, with appropriate R rated fuses fitted.
2
It is critical that the circuit breaker and associated protection relay are set to trip <150 ms. Failure to do so could result
in SCR rupture and subsequent arc fault.
3
Excludes contactors and/or circuit breakers.