PROGRAMMING MENU
Page 36
MVS User Manual
710-13019-00A
8D – Display A or kW
Options:
Current (Default)
Motor kW
Description:
Selects whether the MVS will display current (amperes) or motor kilowatts on the main
monitoring screen.
8E, 8F, 8G, 8H – User-Programmable Screen
Options:
Blank
Displays no data in the selected area, allowing long messages to be shown
without overlapping.
Starter State
The starter's operating state (starting, running, stopping or tripped). Only
available for top left and bottom left positions on the screen.
Motor Current
The average current measured on three phases.
Motor pf
The motor's power factor, measured by the soft starter.
Mains Frequency
The average frequency measured.
Motor kW
The motor's running power in kilowatts.
Motor HP
The motor's running power in horsepower.
Motor Temp
The motor's temperature, calculated by the thermal model.
kWh
The number of kilowatt hours the motor has run via the soft starter.
Hours Run
The number of hours the motor has run via the soft starter.
Analog Input
Not applicable to this product.
Mains Voltage
The average voltage measured on three phases.
Description:
Selects which information will be displayed on the programmable monitoring screen.
8E
User Screen - Top Left
Default: Starter State
8F
User Screen - Top Right
Default: Blank
8G
User Screen - Bottom Left
Default: kWh
8H
User Screen - Bottom Right
Default: Hours Run
8I, 8J, 8K, 8L – Performance Graphs
The MVS has a real-time performance graph to report the behaviour of critical operating parameters.
Parameter 8I
Graph Data
Options:
Current (% FLC) (Default) Current as a percentage of motor full load current.
Motor Temp (%)
Motor temperature as a percentage of the motor rated current
(calculated by the soft starter's thermal model).
Motor kW (%)
Motor kilowatts. 100% is motor FLC (parameter 1A) multiplied
by mains reference voltage (parameter 8N). Power factor is
assumed to be 1.0.
3 . V . I
FLC
. pf
1000
Motor kVA (%)
Motor kilovolt amperes. 100% is motor FLC (parameter 1A)
multiplied by mains reference voltage (parameter 8N).
3 . V . I
FLC
1000
Motor pf
Motor power factor, measured by the soft starter.
Voltage (% Mains)
The average voltage measured on three phases as a percentage
of the mains reference voltage parameter 8N.
Description:
Selects which information the graph will display.
Parameter 8J
Graph Timebase
Options:
10 seconds (Default)
30 seconds
1 minute
5 minutes
10 minutes
30 minutes
1 hour
Description:
Sets the graph time scale. The graph will progressively replace the old data with new data.
Parameter 8K
Graph Maximum Adjustment
Range:
0% – 600%
Default: 400%
Description:
Adjusts the upper limit of the performance graph.