APPENDIX
710-13019-00A
MVS User Manual
Page 59
11.1
Parameter Defaults
If you require assistance from your supplier or a service technician, please note all parameter settings in the table below.
1
Primary Motor Settings
User Set 1
User Set 2
Default
1A
Motor Full Load Current
100 A
1B
Locked Rotor Time
00m:10s
1C
Locked Rotor Current
600% FLC
1D
Motor Service Factor
105%
2
Start/Stop Modes-1
2A
Start Mode
Constant current
2B
Start Ramp Time
00m:01s
2C
Initial Current
400% FLC
2D
Current Limit
400% FLC
2E
Reserved
2F
Kickstart Time
0 ms
2G
Kickstart Level
500% FLC
2H
Stop Mode
Coast to stop
2I
Stop Time
00m:00s
3
Auto-Start/Stop
3A
Reserved
3B
Reserved
3C
Auto-Stop Type
Off
3D
Auto-Stop Time
00h:01m
4
Protection Settings
4A
Excess Start Time
00m:20s
4B
Excess Start Time-2
00m:20s
4C
Undercurrent
20% FLC
4D
Undercurrent Delay
00m:05s
4E
Instantaneous Overcurrent
400% FLC
4F
Instantaneous Overcurrent Delay
00m:00s
4G
Phase Sequence
Any sequence
4H
Current Imbalance
30%
4I
Current Imbalance Delay
00m:03s
4J
Frequency Check
Start/Run
4K
Frequency Variation
±5 Hz
4L
Frequency Delay
00m:01s
4M
Restart Delay
00m:10s
4N
Motor Temperature Check
Do not check
4O
Ground Fault Level
10 A
4P
Ground Fault Delay
00m:03s
4Q
Undervoltage
100 V
4R
Undervoltage Delay
00m:05s
4S
Overvoltage
7200 V
4T
Overvoltage Delay
00m:05s
4U
Instantaneous Overcurrent S2
4400 A
4V
Instantaneous Overcurrent Delay S2
10 ms
5
Auto-Reset Trips (Reserved)
5A
Reserved
6
Inputs
6A
Input A Function
Motor set select
6B
Input A Name
Input trip
6C
Input A Trip
Always active
6D
Input A Trip Delay
00m:00s
6E
Input A Initial Delay
00m:00s
6F
Input B Function
Input trip (N/O)
6G
Input B Name
Input trip
Section 11
Appendix