INSTRUCTIONS
18
Profinet Card (710-16502-00C)
Input
Parameter data from the starter is reported in input bytes 60-63.
Device > controller input bytes are structured as follows.
Byte
Bits
Details
60
0 to 7
Echo parameter number
61
0
1 = Invalid parameter number
1
1 = Invalid parameter value
2 to 7
Reserved
62
0 to 7
Low byte parameter value read from soft starter
63
0 to 7
High byte parameter value read from soft starter
7.4
Trip codes
Trip code Description
255
No trip
1
Excess start time
2
Motor overload
3
Motor thermistor
4
Current imbalance
5
Frequency
6
Phase sequence
7
Overcurrent
8
Power loss
9
Undercurrent
10
Heatsink overtemperature
11
Motor connection
12
Input A trip
13
FLC too high
14
Unsupported option (function not available in inside delta)
15
Communications card fault
16
Network communication
18
Overvoltage
19
Undervoltage
23
Parameter out of range
24
Input B trip
26
L1 phase loss
27
L2 phase loss
28
L3 phase loss
29
L1-T1 shorted
30
L2-T2 shorted