Installation & Operation Manual
94
Document # LTRT-92224
Mediant 8000
15.3
Electrical Requirements
The site must satisfy the following electrical requirements for the proper Mediant 8000
installation.
Table
15-4: Electrical Requirement
Item
Requirement
Power Feeding
In order to maintain the full HA capabilities of the system, a centralized DC
power system must be used as specified in UL60950-1, CAN/CSA-C22.2 NO
60950-1-03 Annex NAB.
Outlets
DC outlets are required for connecting the Mediant 8000. For more information,
see 'Power System' on page
Circuit breaker
To meet the system power HA scheme, the system should not be current limited
to less than 60A. If a circuit breaker is used, it must be 60A or higher rated.
Power
consumption
A fully occupied Mediant 8000 chassis in a TP-6310 (8+1) DC power
configuration has the following average power consumption:
TP-6310 1494 watts at 48 VDC
A fully occupied Mediant 8000 chassis in a TP-8410 (5+1) DC power
configuration has the following average power consumption:
TP-8410 1200 watts at 48 VDC
Summary of Contents for Mediant 8000
Page 2: ......
Page 33: ...Part I Hardware Overview This part describes the hardware overview of the Mediant 8000 chassis...
Page 34: ......
Page 90: ......
Page 158: ......
Page 264: ......
Page 546: ......
Page 775: ...Part VI Maintenance This part describes the Mediant 8000 maintenance procedures...
Page 776: ......
Page 834: ......
Page 879: ...Part VIII Appendices This part describes additional Mediant 8000 configuration procedures...
Page 880: ......
Page 924: ...Media Gateway Mediant 8000 www audiocodes com Installation Operation Maintenance Manual...