3.7.2.1 - List of parameters
Access
conditions
Parameter
n
o
Definition
Possible values
Factory set
values
Manufacturer
01
Number of power stages
2; 3; 4; 5;
or
6
6
02
Maximum boiler temperature (TCMA)
(1)
21
to
80
o
C
80
o
C
03
Minimum boiler temperature (TCMI)
(1)
21
to TCMA
o
C
30
o
C
04
Presence of an ambient temperatute thermostat or sensor
(without =
0;
thermostat =
1;
sensor =
2
)
0; 1
or
2
0
if
04 = 1
or
2
05
Heating pump for ambient temperature control
(no =
0;
yes =
1
)
0
or
1
0
if
04 = 1
or
2
06
Automatic adjustment or automatic correction of the heating
curve or of the set temperature (no =
0;
yes =
1
)
0
or
1
(2)
0
07
Exterior sensor (no =
0;
yes =
1
)
0
or
1
0
if
07 = 1
08
Maximum exterior temperature (TEMA)
(1)
11
to
25
o
C
20
o
C
if
07 = 1
09
Minimum exterior temperature (TEMI)
(1)
-
30
to +
10
o
C
-
5
o
C
if
07 = 1
10
Automatic changeover to summer mode (no =
0;
yes =
1
)
0
or
1
0
11
Time delay for engaging and disengaging between 2 stages
1
to
6
mn
(3)
2 mn
12
Domestic hot water production (no =
0;
yes =
1
)
0
or
1
0
if
12 = 1
13
Domestic water sensor (no =
0;
yes =
1
)
0
or
1
(4)
0
if
13 = 1
14
Anti-legionellosis cycle (no =
0;
yes =
1
)
0
or
1
(5)
0
15
Pairing of power stages
0
or
1
0
16
Engaging of 6 power stages (no =
0;
yes =
1
)
0
or
1
1
if
16 = 0
17
Engaging of stage 1 (no =
0;
yes =
1
)
0
or
1
1
if
16 = 0
18
Engaging of stage 2 (no =
0;
yes =
1
)
0
or
1
1
if
16 = 0
19
Engaging of stage 3 (no =
0;
yes =
1
)
0
or
1
1
if
16 = 0
20
Engaging of stage 4 (no =
0;
yes =
1
)
0
or
1
1
if
16 = 0
21
Engaging of stage 5 (no =
0;
yes =
1
)
0
or
1
1
if
16 = 0
22
Engaging of stage 6 (no =
0;
yes =
1
)
0
or
1
1
23
Purpose
of timer
input*
0
= no purpose
0; 1; 2
or
3
0
1
= boiler set temperature in ECO mode
2
= boiler set temperature in FROST
PROTECTION mode
3
= authorisation of DHW production
Manufacturer
24
Water pressure sensor
0
or
1
1
(1)
See § «Heating curve» for defining based on the following 4 parameters (TCMA, TCMI, TEMA and TEMI)
(2)
This function is not allowed with an ambient temperature thermostat with timer (yes =
1
is not possible with an ambient temperature thermostat with timer)
(3)
Depending on the water flow rate and the volume of water in the heating installation, the boiler may cycle rapidly (risk of wearing).
To reduce the number of start-ups/stops, raise the time delay.
(4)
No =
0
= with electromechanical aquastat (the setting of the desired temperature is carried out on the aquastat itself and not on the control panel.
There is no frost protection of the domestic hot water.
Yes =
1
= sensor with variable resistance. There is frost protection of domestic hot water.
(5)
Caution: for anti-legionellosis protection, the DHW is raised to 65
o
C. The placement of a thermostatic mixing valve on the DHW outlet is mandatory to prevent risks
of burns.
* see
§
«Designated purpose of timer input».
Note: to reset the automatic adjustment to default, set
PAR.06
to
0
, then set it back to
1
.