AUMA Matic Positioner 

Calibration Instruction 

AUMA Actuators, Inc. USA

 

 

All information in this document is subject to change without notice.

 

 

• 

The optional RWG 4-20ma feedback transmitter, if supplied, must be calibrated prior to positioner calibration.  
Refer to the AUMA SA or SG.1 Operation Instruction Manual for calibration instructions. 

NOTE:

  Verify proper limit switch setting prior to positioner calibration. 

Calibration Procedure

 

Positioner adjustment end position CLOSED (standard version) 

 

NOTE:

 

Prior to the positioner setting it has to be ensured that the limit and torque switching of the 
actuator as well as the position feedback have been set.

 

 

• 

Set selector switch (local controls) to position LOCAL. 

• 

Run actuator by pressing push-button 

 to 

end position CLOSED

• 

Supply nominal value E1 of 0 or 4 mA (see wiring diagram). 

• 

Turn potentiometer P10 (t

off

) counter-clockwise to the stop (Figure 3). 

 
NOTE:

 

Missing signals E1/E2 or wrong polarity are indicated by LED V10 ”E1/E2 < 4 mA” (Figure 3)

 

 

Possible LED indication: 

(refer to Figure 3)

 

Required setting in end position CLOSED 

(refer to Figure 3) 

LEDs are not illuminated 

Turn potentiometer ”0” (P3) slightly clockwise until 
LED 

 (V27 yellow) lights up. 

LED 

 (V28 green) is 

illuminated 

Turn potentiometer ”0” (P3) slightly clockwise until LED 

 (V28 

green) goes out and LED 

 (V27 yellow) lights up. 

If

 

LED 

 (V27 yellow) is 

illuminated 

Then

 

Turn potentiometer ”0” (P3) counter-clockwise until LED 

 

(V27yellow) goes out. 
Then turn potentiometer ”0” (P3) slightly clockwise until LED 

 

(V27 yellow) lights up again. 

 

Positioner adjustment end position OPEN (standard version) 

 

• 

Run actuator by pressing push-button 

 (local controls) to 

end position OPEN. 

• 

Connect max. command signal (nominal value E1) = 20 mA. 

 

Possible LED indication: 

(refer to Figure 3)

 

Required setting in end position OPEN 

(refer to Figure 3) 

LEDs are not illuminated 

Turn potentiometer ”max” (P4) slightly counter-clockwise until 
LED 

 (V28 green) lights up. 

LED 

 (V28 green) is 

illuminated 

Turn potentiometer ”max” (P4) clockwise until LED 

 (V28 

green) goes out. 
Then turn potentiometer ”max” (P4) slightly counter-clockwise  
until LED 

 (V28 green) lights up again.  

If

 

LED 

 (V27 yellow) is 

illuminated 

Then

 

Turn potentiometer ”max” (P4) slightly counter-clockwise until 
LED 

 (V27 yellow) goes out and LED 

 (V28 green) lights up.

ISSUE 02/02 

Page 6 of 11 

SE-SI-35-0007 

 

Summary of Contents for Matic Series

Page 1: ...ontrol Accurate positioning is attained through the use of a precision position feedback potentiometer or current device RWG current transmitter The controller drives the motor reversing starters whic...

Page 2: ...he NEMA rating for the enclosure furnished Connect field wiring according to wiring diagram supplied If drawing is not available contact the nearest AUMA office with the Sales Order or Serial Number l...

Page 3: ...que seating in the clockwise direction Switch S3 2 In position 1 the actuator is set for limit seating in the counterclockwise direction In position 2 the actuator is set for torque seating in the cou...

Page 4: ...orrect Verify the field wiring matches electrical drawing supplied by AUMA Fuses are open CAUTION Before checking replacing fuses ensure all power is disconnected Remove selector switch push button co...

Page 5: ...ent FINE SENSITIVITY This control adjustment determines the amount of error signal that occurs before the Sens P7 motor is energized in the direction determined by the input signal This is only used f...

Page 6: ...in end position CLOSED refer to Figure 3 LEDs are not illuminated Turn potentiometer 0 P3 slightly clockwise until LED V27 yellow lights up LED V28 green is illuminated Turn potentiometer 0 P3 slight...

Page 7: ...To prevent exceeding the max permissible number of starts refer to Technical data sheet SG SAR or consult factory in extreme cases a time delay between 0 5s left stop and 10s right stop may be set wit...

Page 8: ...ow lights up LED V27 yellow is illuminated Turn potentiometer max P4 clockwise until LED V27 yellow goes out Then turn potentiometer max P4 slightly counter clockwise until LED V27 yellow lights up ag...