Max. lenght (m) from the lines of drives to the contol unit -
ONE
locking drive
OFV1
cable length (m) of the locking drive
OFV1
:
1,5 m
2,0 m
2,5 m
3,0 m
3,5 m
4,0 m
Cut-off curr
ent
of the opening drive
0,8 A
90 150 240 360 88 147 235 352 86 143 230 344 84 140 224 336 82 137 219 328 80 133 214 320
1,2 A
58 97 155 232 56 93 149 224 54 90 144 216 52 87 139 208 50 83 133 200 48 80 128 192
1,6 A
42 70 112 168 40 67 107 160 38 63 101 152 36 60 96 144 34 57 91 136 32 53 85 128
2,4 A
26 43 96 104 24 40 64 96 22 37 59 88 20 33 53 80 18 30 48 72 16 27 43 64
3,0 A
20 33 52 78 18 29 47 70 16 26 42 62 14 23 36 54 12 19 31 46 10 16 26 38
1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0
Line cross-section (mm
2
) from the lines of drive to the control unit
i
nstructiOns
On
cOnnectiOn
: m
ax
.
Lenght
FrOm
the
Lines
OF
driVes
tO
the
cOntrOL
unit
Max. lenght (m) from the lines of drives to the contol unit -
TWO
locking drive
OFV1
cable length (m) of the locking drive
OFV1
:
1,5 m
2,0 m
2,5 m
3,0 m
3,5 m
4,0 m
Cut-off curr
ent
of the opening drives
0,8 A
45 75 120 180 44 74 118 176 43 72 115 172 42 70 112 168 41 69 110 164 40 67 107 160
1,2 A
29 49 78 116 28 47 75 112 27 45 72 108 26 44 70 104 25 42 67 100 24 40 64 96
1,6 A
21 35 56 84 20 34 54 80 19 32 51 76 18 30 48 72 17 29 46 68 16 27 43 64
2,4 A
13 22 35 52 12 20 32 48 11 19 30 44 10 17 27 40 9 15 24 36 8 14 22 32
3,0 A
10 17 26 39 9 15 24 35 8 13 21 31 7 12 18 27 6 10 16 23 5 8 13 19
1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0
Line cross-section (mm
2
) from the lines of drive to the control unit
Max. lenght (m) from the lines of drives to the contol unit -
THREE
locking drive
OFV1
cable length (m) of the locking drive
OFV1
:
1,5 m
2,0 m
2,5 m
3,0 m
3,5 m
4,0 m
Cut-off curr
ent
of the opening drives
0,8 A
30 50 80 120 29 49 78 117 29 48 77 115 28 47 75 112 27 46 73 109 27 44 71 107
1,2 A
19 32 52 77 19 31 50 75 18 30 48 72 17 29 46 69 17 28 44 67 16 27 43 64
1,6 A
14 23 37 56 13 22 36 53 13 21 34 51 12 20 32 48 11 19 30 45 11 18 28 43
2,4 A
9 14 23 35 8 13 21 32 7 12 20 29 7 11 18 27 6 10 16 24 5 9 14 21
3,0 A
7 11 17 26 6 10 16 23 5 9 14 21 5 8 12 18 4 6 10 15 3 5 9 13
1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0 1,5 2,5 4,0 6,0
Line cross-section (mm
2
) from the lines of drive to the control unit
Select the following values (see the tables below):
• number of the locking drives
OFV1
• cut-off current of the opening drive
• measure the cable length of the locking drive
OFV1
Be determined the
line cross-section
from the lines of
drive to the control unit and the
cable length
of
the locking drive
OFV1
.
To calculate can also be used the line calcu-
lation program. Details can be found on our
website:
(www.aumueller-gmbh.de)
n
Ote
07
07