SPECIFICATION 

MODEL 

 

 

AURO 1200/2200 

CAPACITY   

VA/W 

1200VA/600W 

2200VA/1100W 

INPUT 

Voltage 

120VAC or 230VAC   

Voltage Range 

85-145VAC or 170-280VAC 

OUTPUT 

Voltage 

110/120VAC or 220/230/240VAC 

Voltage Regulation (Batt. Mode) 

+/-10% 

Frequency 

50Hz or 60Hz 

Frequency Regulation (Batt. Mode) 

+/-1 Hz   

Output Waveform 

Modified Sine wave 

BATTERY 

Battery Type 

12V7Ah x 2 

12V/9Ah x 2 

Recharge Time 

6 hours to 90% after complete discharge 

TRANSFER 
TIME 

Typical 

4-8 ms 

INDICATOR 

AC Mode 

Green lighting 

The 4st Green Led Lighting. 

Optional -- (The 1st to 3th green Led lighting to indicate load level) 

LED1 (green): >66% load level. 
LED2 (green): >33% load level. 

LED3 (green): >0% load level. 

Backup Mode 

Green flashing 

The 4st green blinking. 

Optional -- (The 1st to 3th green Led lighting to indicate battery 

capacity) 

LED1 (green): battery voltage > 12.5V. 

LED2 (green): battery voltage > 11.5V. 

LED3 (green): battery voltage > 10.5V. 

AUDIBLE 
ALARM 

Backup Mode 

Sounding every 10 seconds 

Low Battery 

Sounding every 1second 

Overload 

Sounding every 0.5 second 

Fault 

Continuously sounding 

PROTECTION 

Full Protection 

Discharge, overcharge, and overload protection 

PHYSICAL 

Dimension (mm), DXWXH 

365(L)x139(W)x195(H)   

WEIGHT 

Net Weight 

8.6kgs 

  10.2kgs 

ENVIRONMENT 

Operating Environment 

0°C - 40°C 

Noise Level 

Less than 40dB 

 

Summary of Contents for 1.2K

Page 1: ...User s Manual AURORA 1 2K 2 2K Uninterruptible Power System...

Page 2: ...the UPS in locations where there is standing or running water or excessive humidity Do not plug the UPS input into its own output Do not attach a power strip or surge suppressor to the UPS Do not att...

Page 3: ...rom the mains hazardous voltage still may be accessible through supply from battery The battery supply should be therefore disconnected in the plus and minus pole of the battery when maintenance or se...

Page 4: ...Overload of the UPS 1 Remove some non critical load 2 Battery voltage is too low 2 Charge battery 8 hours or more 3 Battery defect due to high temperature operation environment or improper operation...

Page 5: ...turn it to the place of purchase 2 Charging This unit is shipped from the factory with its internal battery fully charged however some charge may be lost during shipping and the battery should be rech...

Page 6: ...the ambient temperature or humidity is high On the other hand place the UPS away from the monitor at least 20cm to avoid interference 4 Connection Plug the UPS into a 2 pole 3 wire grounded receptacl...

Page 7: ...the UPS when AC utility power is not available simply press the power switch 7 Green Power Function All Aurora UPS is equipped with Green Power Function For saving power and protecting battery the me...

Page 8: ...to 3th green Led lighting to indicate load level LED1 green 66 load level LED2 green 33 load level LED3 green 0 load level Backup Mode Green flashing The 4st green blinking Optional The 1st to 3th gre...

Reviews: