background image

INSTRUCTION FOR REPAIRING APPLIANCES CONTAINING R 290

AUTHORISED PERSONS ONLY!

         f) Make sure the cylinder is situated on the scales before recovery takes place.
        g) Start the recovery machine and operate in accordance with manufacturer's instructions.
        h) Do not overfill cylinders. (no more than 80% volume liquid charge).
         i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
         j) When the cylinders have been filled correctly and the process completed, make sure that the 
            cylinders and the equipment are removed from site promptly and all isolation valves on the 
            equipment are closed off.
        k) Recovered refrigerant shall not be charged into another refrigerant system unless it has been 
            cleaned and checked.

18. Labelling 
    

Equipment shall be labelled stating that is has been de-commissioned and emptied of refrigerant. 

    The label shall be dated and signed. Ensure that there are labels on the equipment stating the 
    equipment contains flammable refrigerant.

19. Recovery 
    

When removing refrigerant from a system, either for servicing or de-commissioning, it is 

    recommended good practice that all refrigerants are removed safely.
    When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery 
    cylinders are employed. Ensure that the correct number of cylinders for holding the total system 
    charge are available. All cylinders to be used are designated for the recovered refrigerant and 
    labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be 
    complete with pressure relief valve and associated shut-off valves in good working order. Empty 
    recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
    The recovery equipment shall be in good working order with a set of instructions concerning the 
    equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.
    In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses 
    shall be complete with leak-free disconnect couplings and in good condition. Before using the 
    recovery machine, check that it is in satisfactory working order, has been properly maintained and 
    that any associated electrical components are sealed to prevent ignition in the event of a refrigerant 
    release. Consult manufacturer if in doubt.
    The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, 
    and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and 
    especially not in cylinders.
    If compressors or compressor oils are to be removed, ensure that they have been evacuated to an 
    acceptable level to make certain that flammable refrigerant does not remain with the lubricant. The 
    evacuation process shall be carried out prior to returning the compressor to the suppliers. Only 
    electric heating to the compressor body shall be employed to accelerate this process. When oil is 
    drained from a system, it shall be carried out safely.

20. Transport of equipment containing flammable refrigerants
    

Compliance with transport regulations

21. Discarded appliances supplies flammable refrigerants
    

See national regulations

22. Storage of equipment/appliances
    

The storage of equipment should be in accordance with the manufacturer's instructions.

23. Storage of packed (unsold) equipment
    

Storage package protection should be constructed such that mechanical damage to the equipment 

    inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces 
    of equipment permitted to be stored together will be determined by local regulations.

24. Marking equipment using signs
    

See local regulations.

13

Summary of Contents for WDH-716DE

Page 1: ...NG 2 3 CAUTIONS 4 5 DESCRIPTION OF COMPONENTS FUNCTION EXPLANATION 6 OPERATING INSTRUCTIONS 7 CONTINUOUS DRAINAGE OPTIONS 8 MAINTENANCE EMERGENCY 9 R290 AUTHORISED REPAIRER INSTRUCTIONS 10 13 SPECIFICATIONS LAST PAGE ...

Page 2: ...inimum of once every two weeks Do not place the appliance near any heating appliance The appliance should be transported upright Any internal water should be emptied before transporting Do not turn the appliance on for at least one hour after transporting it Flammable substances or pressurised containers aerosol cans should be kept a minimum of 50cms away from the appliance The appliance should no...

Page 3: ...perating electrical heater A surface area greater than 4 m is necessary for the installation use and storage of the appliance Do not pierce or burn the appliance Do not perforate any of the components in the refrigerant circuit Refrigerant gas may be odourless Use care when storing the appliance Stagnation of possible leaks of refrigerant gas in unventilated rooms could lead to fire or an explosio...

Page 4: ...ower plug If the power cord on this unit is damaged it must be replaced by the manufacturer it s service agent or qualified persons in order to avoid a hazard CAUTIONS CAUTIONS Do not place anything on top of the control panel Do not place anything over the air inlet or air outlet Do not let children play with the unit or control panel Do not wet the machine or the control panel Keep flammable gas...

Page 5: ... parts or start a fire Do not place the machine on uneven ground This may cause shaking noise and leakage of water It is dangerous to put anything into the machine Keep the machine away from any type of heat sources 5 Keep the unit 20cm away from the wall to dissipate the heat properly Close all windows and doors to assist with the efficiency of removing moisture ...

Page 6: ... setting of auto switch on off The indicator is on when the defrost function is in operation Bucket full indicator the machine will stop running Low fan speed High fan speed LCD display Water tank is full when illuminated DESCRIPTION OF COMPONENTS FUNCTION EXPLANATION 6 CONTROL PANEL OUTLET FOR DEHUMIDIFIED DRY AIR DRAIN BUCKET AIR FILTER CONTINUOUS DRAINAGE OUTLET ROLLER CASTORS MOIST AIR INTAKE ...

Page 7: ... water tank to the correct position When Bucket Full Light Is On When the water tank is full the machine will stop and the Bucket Full light will illuminate The water tank should be carefully removed from the machine by sliding it outwards from the front of the machine and it should be emptied When the empty tank is replaced properly into the machine the machine will start up and run normally When...

Page 8: ...ions for drainage near the dehumidifier Drain hose Back of the unit Drain hose 3 Connect the drain hose to the drainage outlet Drain cap 1 Prepare hose to drain out water The hose has inner diameter of 13mm 2 Unscrew drain cap of the drainage outlet and remove soft rubber cover CONTINUOUS DRAINAGE OPTIONS Continuous drainage outlet Soft cover Drain cap INSTALLING DRAINAGE HOSE When using continuou...

Page 9: ...e dehumidifier EMERGENCY Air filter cleans the dust and impurities from the air which may hinder the dehumidifying function these should be regularly cleaned The filter is located behind the rear grill and should be pulled outwards from the top to remove Clean with a vacuum cleaner or wash it with clean water and dry with a dry cloth Replace filter and continue to operate the dehumidifier 9 ...

Page 10: ...of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly be released to the surrounding space Prior to work taking place the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition r...

Page 11: ...uipment in use Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Replace components only with parts specified by the manufacturer Other parts may result in the ignition of refrigerant in the atmosphere from a leak 12 Cabling Check that cabling will not be subject to wear corr...

Page 12: ...ts shall be followed Ensure that contamination of different refrigerants does not occur when using charging equipment Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them Cylinders shall be kept upright Ensure that the refrigeration system is earthed prior to charging the system with refrigerant Label the system when charging is complete if not alrea...

Page 13: ... good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants In addition a set of calibrated weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory worki...

Page 14: ...isposed of with household waste Please recycle where facilities exist Check your local authority of retailer for recycling advice SPECIFICATIONS 14 WDH 716DE 420 W 20 362 x 582 x 270 mm 13 kg SAA approval 0 086 kg Certificate No TUV 025466 EA ...

Reviews: