Ack Required for Off-Normal, 
Fault, and Normal

 

Requires a control module acknowledgement for each 
message type. Normally not required.  

TIP

  To require operator acknowledgement for an Alarm 

or Return-to-normal message (stored in the WebCTRL 
database) change the acknowledgement settings on 
WebCTRL's 

Alarm > Enable/Disable

 tab for an alarm 

source or an alarm category.  

Recipient List

 

 

Recipients

 

The first row in this list is the WebCTRL Server. Do not 
delete this row. Click 

Add 

if you want other BACnet 

devices to receive alarms. 

Recipient Description 

Name that appears in the 

Recipients 

table.

 

Recipient Type 

Use 

Address 

(static binding) only for third-party BACnet 

device recipients that do not support dynamic binding.

 

Recipient Device Object 
Identifier 

Type the 

Device Instance

 from SiteBuilder (or from the 

network administrator for third-party devices) in the 

#

 

field.

 

Process Identifier 

Change for third-party devices that use a BACnet Process 
Identifier other than 1. WebCTRL processes alarms for 
any 32-bit Process Identifier.

 

Issue Confirmed 
Notifications

 

Select to have a device continue sending an alarm 
message until it receives delivery confirmation from the 
recipient. 

 

Common Alarms 

On these pages, you can change the following control module alarm 
properties: 

 

BACnet alarm object properties 

 

Enable/disable 

 

Delays 

NOTE

  To set up alarm actions for control module generated alarms, see 

Setting up alarm actions

 in WebCTRL Help. 

  

Module Generated Alarm

 

 

Description

 

Short message shown on WebCTRL's Alarm page or in an 
alarm action when this type of alarm is generated. 

Events

 

 

Alarm Category and Alarm 
Template

 

See 

Customizing alarms

 in WebCTRL Help. 

Enable

 

Clear these checkboxes to disable Alarm or Return to 
normal messages of this type from this control module. 

Notification Class

 

Do not change this field. 

 

Custom Translation 
Tables 

On the 

Custom Translation Table

 pages, you can edit the tables used to 

translate raw sensor data to engineering units for inputs associated with 

Non-Linear, Custom Table

 sensor/actuator types. 

 

ZN551 Control Module • Rev. 3/17/2005

 

15 

© 2005 Automated Logic Corporation   

 

Summary of Contents for ZN551

Page 1: ...re the flow sensor to the control module 12 To set up the Airflow Control microblock 12 To set up the module driver 13 Driver 13 Device 14 Notification Class 1 14 Common Alarms 15 Custom Translation Tables 15 To communicate through the local access port 16 To set up a Local Access connection in WebCTRL 16 Troubleshooting 16 Formatting the control module 17 LED s 17 Manufacture date 18 Compliance 1...

Page 2: ...d 2 are also configurable for 0 5 Vdc Inputs 4 and 5 are used when a LogiStat sensor is connected but are available if an RS room sensor is connected Input resolution 10 bit A D Digital outputs 5 digital outputs relay contacts rated at 1 A max 24 Vac Vdc Configured normally open Analog output 1 analog output 0 10 Vdc 5 mA max Output resolution 8 bit D A Memory 512 kB non volatile battery backed RA...

Page 3: ...t when the contacts are closed IN 1 IN 2 0 5 Vdc The output impedance of a 0 5 Vdc source must not exceed 100 Ohms The input impedance of the ZN551 is approximately 30 kOhm IN 4 IN 5 LogiStat IN 4 See Thermistor IN 5 Setpoint adjust Input voltages should be from 1 4 3 4 Vdc NOTE A LogiStat sensor connected to the ZN551 uses IN 4 and IN 5 An RS room sensor connected to the Rnet port does not use th...

Page 4: ...e same transformer that powers the ZN551 NOTE You can power several control modules from the same transformer if you maintain the same polarity To wire for power 1 Remove power from the 24 Vac transformer 2 Pull the screw terminal connector from the control module s power terminals labeled Gnd and 24 Vac 3 Connect the transformer wires to the screw terminal connector 4 Apply power to the transform...

Page 5: ...P communicating at 9600 bps 19 2 kbps 38 4 kbps or 76 8 kbps NOTE ARC156 is a unique implementation of the industry standard ARCNET For a summary of differences between ARCNET and ARC156 see the ARC156 Wiring Technical Instructions http info automatedlogic com For Use Maximum Length ARC156 22 AWG low capacitance twisted stranded shielded copper wire 2000 feet 610 meters MS TP A dedicated 22 AWG to...

Page 6: ...et 305 meters 26 AWG Shielded Thermistor Dry contact 1000 feet 305 meters 22 AWG Shielded RS room sensors 500 feet 152 meters 22 AWG 4 conductor1 Shielded or unshielded LogiStat 100 feet 30 meters 22 AWG2 Unshielded 1 See the RS Room Sensors Technical Instructions http info automatedlogic com 2 See the LogiStat Sensors Technical Instructions http info automatedlogic com Output wiring To size outpu...

Page 7: ...ort to the terminal of the same name on the RS room sensor NOTE If wiring an RS room sensor with shielded wire connect the shield wire to the GND terminal with the ground wire For a LogiStat room sensor use the following table Wire this terminal on the LStat port To this terminal on the LogiStat sensor Gnd IN 4 IN 5 LED Gnd Temp SW LS5v 5 Set the appropriate jumpers on the ZN551 To use For IN 1 or...

Page 8: ... V Motor Valve Any AO Gnd Any AO NOTE Current from the analog outputs can drive a 20 mA device To use an analog output for this purpose you may need to add a 1 2 watt resistor in series with the device to achieve the required total resistance of 500 Ohms For example to drive a device that has 100 Ohms of resistance wire a 400 Ohm resistor in series with the 20 mA device to achieve 500 Ohms resista...

Page 9: ...local copy of the system database to the ZN551 s local access port See steps 1 3 of To communicate through the local access port page 16 To download memory in WebCTRL 1 On WebCTRL s CFG tree click Download 2 Select the Memory checkbox NOTE A memory download includes a Parameters and Schedules download 3 On the Network tree on the right select the control module you want to download to 4 Click Add ...

Page 10: ...e Engineering values associated with 0 Vdc Min and 5 Vdc Max 1 Thermistor Thermistor Select your Thermistor type or set up and select a Non Linear Custom Table2 N A Digital Binary BBI Dry Contact Dry Contact N A N A Input values 1 The sensor reads a value and sends a corresponding signal Volt mA or psi to the ZN551 s physical input The Analog Input microblock uses the Min and Max values to linearl...

Page 11: ...ol program uses 13 7 for any calculations downstream from the microblock Analog Output BAO The driver truncates the wire input value to the microblock before performing any scaling calculations EXAMPLE If the wire input value is 13 789 and you set the Resolution to 0 1 the microblock uses 13 7 for any scaling calculations Digital Inputs and Outputs N A Offset Polarity values Offset Polarity is not...

Page 12: ...with each actuator connected to two digital outputs To connect the duct tubes to the flow sensors USF 1 Connect the duct s total pressure tube to the USF s High connector 2 Connect the duct s static pressure tube to the USF s Low connector UDF Follow the procedure for a USF but connect one duct s tubes to the UDF s Flow 1 connectors and the other duct s tubes to the UDF s Flow 2 connectors To wire...

Page 13: ...he left of Flow Input AI Configuration 6 In the Sensor Type field under Calibration select No Translation 7 On the Logic page select the airflow control microblock for Flow 2 8 Repeat steps 2 through 6 for Flow 2 typing 2 in step 3 NOTE When performing test and balance follow the steps under Test and Balance on the Airflow Control microblock s Properties page Details tab in WebCTRL To set up the m...

Page 14: ...rent network is an MS TP network Notification Class 1 WebCTRL alarms use Notification Class 1 A BACnet alarm s Notification Class defines Alarm priority for Alarm Fault and Return to Normal states Options for BACnet alarm acknowledgement Where alarms should be sent recipients NOTE You may need to set up additional Notification Classes if your system will handle Life Safety alarms or if you need to...

Page 15: ...ier other than 1 WebCTRL processes alarms for any 32 bit Process Identifier Issue Confirmed Notifications Select to have a device continue sending an alarm message until it receives delivery confirmation from the recipient Common Alarms On these pages you can change the following control module alarm properties BACnet alarm object properties Enable disable Delays NOTE To set up alarm actions for c...

Page 16: ... 4 Relay switch to Network To set up a Local Access connection in WebCTRL 1 On the CFG tree select Connections 2 On the Configure tab click Add 3 From the Type drop down list select BACnet Local Access 4 Optional Edit the Description 5 Type the computer s Port number where your APT is connected 6 Set the Baud rate to 115200 7 Click Accept 8 On the View tab click the drop down arrow next to your de...

Page 17: ...network segment Tx The ZN551 is transmitting data over the network segment DO The digital output is active The Run and Error LED s indicate control module and network status If Run LED shows And Error LED shows Status is 2 flashes per second Off Normal 2 flashes per second 2 flashes alternating with Run LED Five minute auto restart delay after system error 2 flashes per second 3 flashes then off C...

Page 18: ...ear month and day of manufacture The month digit is in hexadecimal format Compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and c...

Reviews: