52
Instructions for the installer
5.5.5 - FIRE PROOF THERMOSTAT
A fire proof thermostat can be connected to the control panel in order to switch off the fan, connected to the terminals BS so as
to arrest combustion in the wood fired boiler.
5.5.6 - WAITING TIME (After Sales Service function)
The default waiting time (Timer 1) is equal to 30 minutes; to make commissioning easy at the boiler installation stage, the mot her
board is equipped with a logical function that allows the waiting time to be reduced to 3 minutes: the installer to gain access to
this function has to position the jumper, supplied with the boiler, between the pins 69 - 70.
WARNING
: The installer, once the commissioning is finished, must remove the a.m. jumper from the terminals 69 - 70, in order
to restore normal operation: the manufacturer declines any responsibility and/or additional costs connected if normal boiler
operation is not restored.
5.5.7 - RETURN FLOW SENSOR (Tr) INSTALLATION
The installation of the accumulator foresees the connection of the return sensor (Tr) to the dedicated terminals (see paragraph
3.12, page 27):
it is necessary that during the installation stage the After Sales Service
removes the jumper placed on the
pins 71 and 72. Otherwise, the Tr sensor failure alarm and the control of the KKP pump for loading the accumulator are inhibite d:
the manufacturer declines any responsibility if this occurs.