background image

Installation and Maintenance

Manual

Industrial Swing Gate Operator

Model: ASA244BS

Made in Australia from Australian & quality imported components

January 2010

N14870

Summary of Contents for ASA244BS

Page 1: ...Installation and Maintenance Manual Industrial Swing Gate Operator Model ASA244BS Made in Australia from Australian quality imported components January 2010 N14870 ...

Page 2: ...e 4 Section 3 Installation Page 4 Electrical Connections Page 6 CB6 Control Board Commissioning Page 8 Section 6 Manual Release Instructions Page 9 Section 4 Maintenance Page 10 Section 5 Warranty Page 11 Annexure Control Board Layout for 24v Operators Schematic Wiring Diagram ...

Page 3: ...y necessary signs to indicate any danger areas and automatic operation of the gate or door The operators are not designed to be used in any hazardous areas or areas subject to flooding etc All electrical connections and wiring must be performed with AS NZS 3000 2007 as the guidelines Or its counterpart for other countries outside of Australia and New Zealand WARNING ELECTRICITY CAN KILL The manufa...

Page 4: ...follows Electrical Cabling A suitably rated Isolator and 240v power supply should be available near to where the gate operator control box is to be mounted If electrical cabling needs to be run across the driveway where the single gate operator is on the opposite side to the control box then ensure the appropriate number of cables see wiring requirements are run in conduit and are installed at the...

Page 5: ...ld tags onto the mounting plate or as a last resort fix the operator straight to the wall preferably using suitable chemical type anchors to ensure a firm mounting is obtained If fixing without mounting plate ensure spacers i e washers or nuts are used between the wall and the operator to allow for the cover to fit Lift operator into position and bolt to the mounting plate Turn the knurled disc an...

Page 6: ... Wires Connect cable to din rail terminals labelled motor 1 Connect shield to earth terminal Control Connect low voltage limit switch wires to limit switch terminals on circuit board Note the common terminal and open close terminals for motor one and motor two Connect shield to earth terminal Control Inputs The P E OPN and STP inputs require a normally closed switch contact and therefore should be...

Page 7: ...le POSITION 3 Light Outputs Warning OFF Optional light module controls a light with timer which turns light off after 60seconds ON Optional light module controls a warning light which activates whenever motors are on POSITION 4 Swipe Mode OSC Input OFF OSC input terminal has standard Open Close Stop action ON OSC input terminal will only open the door gate The input also resets the P E triggered a...

Page 8: ...button is released or the limit switches are reached The OPN status LED on the control board will flash at 1 second intervals to assist setting times Note when setting the OPEN and CLOSE cycle times when limit switches are used release the push button a few seconds after the limit switch cuts motor power This allows for the motors to slow down over the life of the operators without the need to adj...

Page 9: ...pen side door on gate operator cover Turn knurled disc anticlockwise for arm to be released from gearbox If a magnetic lock is fitted turn off the power to the control box If an electric lock is fitted release with the electric lock key provided The gate will now open manually Ensure gate is held firm so it does not close on someone or something To engage drive turn knurled knob clockwise until ti...

Page 10: ...perator isolate the electrical supply to ensure operator will not run inadvertently Gate hinges in good condition and oiled greased Gate swings freely Gate stops in good condition Gate operator mounting bolts tight All arm joints loose but firm No oil leaks from gearboxes Gearbox drive cogs tight on shafts Gearbox mounting bolts nuts tight Inside operator and control box clean Baygon Surface Spray...

Page 11: ...y in the following circumstances i If no proof of date of purchase can be produced ii If the product has been used in a manner beyond its design parameters iii If the product is tampered with or repaired by personnel not authorised to do so iv In respect of loss or damage caused by rough treatment v If the product is not used and maintained in accordance with instructions or recommendations listed...

Page 12: ......

Page 13: ...2 ...

Page 14: ...service area it may be possible to book a local technician to look at your installation Wait times will vary dependent on local workloads The cost is a service fee which includes the first half hour and the hourly rate thereafter If any Automatic Solutions provided parts are found to be defective and within warranty these will be provided free of charge NOTE If you suspect that any parts are defec...

Reviews: