Automatic Systems
PNG38X-A3_1-04-gb-02.doc
10/12/01
p. 38/51
4.9. Variable speed controller configuration
The VSC EPROM is programmed by means of the DIP switches on the electronic board.
1. Operation mode: set DIP 1 on OFF and DIP 2 on ON.
2. In order to programme the intensive test, set DIP 3 on ON.
3. In order to select the door opening on power failure, set DIP 4 on ON.
4. Door opening:
DIP 5
DIP 6
TIME
DOOR TYPE
0
1
0.3 seconds
1
0
0.4 seconds
Low doors
1
1
0.6 seconds
0
0
0.7 seconds
High doors
Low doors
5. Door closing:
DIP 7
DIP 8
TIME
DOOR TYPE
0
1
0.6 seconds
1
0
0.9 seconds
Low doors
1
1
1.3 seconds
0
0
1.6 seconds
High doors
Low doors
IMPORTANT
:
The equipment you have received is configured as “minimum risk” for users. It is possible to
increase the obstacle closing speed in order to reinforce control and consequently reduce fraud.
As the risk for users is increased in this case, you might have to prohibit access to animals and
unaccompanied children.