The following tables provide the specifications for the F2–02DAS –1, Isolated Analog Output
Module.
NOTE:
One count in the specifications table is equal to one least significant bit of the analog data value (1 in 65536)
Analog Output Configuration Requirements
The F2-02DAS-1 Analog output appears as a 32 discrete output points. The module can be
installed in any slot of a DL205 system, but the available power budget and discrete I/O points
are the limiting factors. Check the DL205 PLC User Manual for the particular model of CPU
and I/O base being used for information regarding power budget and number of local, local
expansion or remote I/O points.
Output Specifications
Number of Channels
2, isolated (2 commons)
Output Range
4–20 mA
Resolution
16 bit (1 in 65536)
Output Type
Current sourcing
Isolation Voltage
±750V continuous, channel to channel, channel to logic
Loop Supply
18–32 VDC
Max Load Impedance
525
q
Linearity Error (end to end)
±10 counts (±0.015% of full scale) maximum
Conversion Settling Time
3ms to 0.1% of full scale
Gain Calibration Error
±32 counts (±0.05%)
Offset Calibration Error
±13 counts (±0.02%)
Output Drift
50ppm / ° C
Maximum Inaccuracy
±0.07% @ 25° C (77° F)
±0.18% 0–60° C (32–140° F)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
b
C
D
General Specifications
PLC Update Rate
1 channel per scan maximum (multiplexing)
2 channels per scan maximum (pointer –
DL240/DL250-1/DL260 only)
Digital Outputs /
Output Points Required
16 binary data bits, 2 channel ID bits;
32 point (Y) output module
Power Budget Requirement
100mA @ 5VDC (supplied by the base)
External Power Supply
18–24 VDC 50mA per channel, Class 2
Operating Temperature
0–60° C (32–140° F)
Storage Temperature
-20 – 70° C (-4 – 158° F)
Relative Humidity
5–95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304