DL205 Analog Manual, 7th Edition Rev. D
16-23
Chapter 16: F2-8AD4DA-2, 8-Ch. In / 4-Ch. Out Analog Voltage Combination
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
C
D
Input Engineering Unit Conversion Example 1:
Data format = BCD,
Channel 1 data memory location = V2000,
Channel 1 resolution = 12 bits,
Channel 1 engineering units = 0.0–140.0 PSI,
Channel 1 input device = 0–5V or 0–10V transmitter.
Input
Engineering Unit Conversion Example 2:
Data format = binary,
Channel 1 data memory location = V2000,
Channel 1 resolution = 14 bits,
Channel 1 engineering units = 0.0–140.0 PSI,
Channel 1 input device = 0–5V or 0–10V transmitter.
NOTE:
The above examples use SP1 (which is always on) as a permissive contact for the engineering unit conversions.
X, C, etc. could also be used as a permissive contact.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
C
D
MUL
K1400
Multiply by 1400;
EU range X 10 for implied decimal.
DIV
K4095
Divide by 4095;
12 bit digital range.
OUT
V2100
Store input EU value in V2100.
LD
V2000
SP1
Load input channel 1 digital value into accumulator.
MULB
K578
Multiply by 1400 [hex 578];
EU range X 10 for implied decimal.
DIVB
K3FFF
Divide by 16383 [hex 3FFF];
14 bit digital range for 0--20mA.
(Use 65535 [KFFFF] for 16 bit; 4095 [KFFF] for 12 bit.)
LD
V2000
SP1
Load input channel 1 digital value into accumulator.
OUT
V2100
Store input EU value in V2100.