background image

1

Sales 800-633-0405

www.productivity2000.com

Terminal Block sold separately, (see wiring options on page 5).

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement. (See www.productivity2000.com for details).











 







I1+
I2+
I3+
I4+

COM
COM
COM
COM
COM
COM

0V

24V+

COM

P2-04AD-1

2000

WARNING:

 

To minimize the risk of potential safety problems, you should 

follow all applicable local and national codes that regulate the installation 

and operation of your equipment. These codes vary from area to area and 

it is your responsibility to determine which codes should be followed, and to 

verify that the equipment, installation, and operation are in compliance with 

the latest revision of these codes.

Equipment damage or serious injury to personnel can result from the 

failure to follow all applicable codes and standards. We do not guarantee 

the products described in this publication are suitable for your particular 

application, nor do we assume any responsibility for your product design, 

installation, or operation.

If you have any questions concerning the installation or operation of this 

equipment, or if you need additional information, please call Technical 

Support at 770-844-4200.

This publication is based on information that was available at the time it 

was printed. At AutomationDirect.com

®

 we constantly strive to improve 

our products and services, so we reserve the right to make changes to 

the products and/or publications at any time without notice and without 

any obligation. This publication may also discuss features that may not be 

available in certain revisions of the product.

Removable Terminal Block Specifications

Part Number

P2-RTB

P2-RTB-1

Number of  

positions

18 Screw Terminals

18 Spring Clamp Terminals

Wire Range

30–16 AWG (0.051–1.31 mm²)
Solid / Stranded Conductor
3/64 in. (1.2 mm) Insulation Maximum
1/4 in (6–7 mm) Strip Length

28–16 AWG (0.081–1.31 mm²)
Solid / Stranded Conductor
3/64 in (1.2 mm) Insulation Maximum
19/64 in (7–8 mm) Strip Length

Conductors

“USE COPPER CONDUCTORS, 75ºC” or equivalent.

Screw Driver 

Width

1/8 in (3.8 mm) Maximum

Screw Size

M2

N/A

Screw Torque

2.5 lb·in (0.28 N·m)

N/A

P2-04AD-1 Analog Input

The P2-04AD-1 Current Analog Input Module provides 

four channels for receiving 0–20 mA signals for use 

with the Productivity2000 system.

Warning  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Removable Terminal Block Specifications. . . . . . . .  1

General Specifications   . . . . . . . . . . . . . . . . . . . . . . 2

Input Specifications  . . . . . . . . . . . . . . . . . . . . . . . . . 2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3

Module Installation Procedure . . . . . . . . . . . . . . . . . 4

QR Code  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Hot Swap Information  . . . . . . . . . . . . . . . . . . . . . . . 4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Module Configuration   . . . . . . . . . . . . . . . . . . . . . . . 5

Linear Scaling  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Non-Linear Scaling  . . . . . . . . . . . . . . . . . . . . . . . . . 6

OLED Panel Display Menus  . . . . . . . . . . . . . . . . . . 7

Diagnostic/Status. . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Summary of Contents for Productivity2000 P2-04AD-1

Page 1: ...ion is based on information that was available at the time it was printed At AutomationDirect com we constantly strive to improve our products and services so we reserve the right to make changes to the products and or publications at any time without notice and without any obligation This publication may also discuss features that may not be available in certain revisions of the product Removable...

Page 2: ...61010 2 201 Safety Input Specifications Input Channel 4 Input Ranges 0 20 mA Signal Resolution 16 bit Resolution Value of LSB least significant bit 0 20 mA 0 305 μA per count 1 LSB 1 count Data Range 0 to 65535 counts Input Type Sinking Single ended 1 common Maximum Continuous Overload 31mA Input Impedance 250Ω 0 1 1 4 W Hardware Filter Characteristics Low Pass 3dB 100Hz Sample Duration Time 9ms p...

Page 3: ...ng fuse is recommended for current loops 24VDC User Supplied Power User Supplied Transmitter Power AC or DC 032A fuse COM I 3 Wire Current Transmitter 3 Wire Transmitter 24VDC User Supplied Power COM I1 I2 I3 I4 COM COM 0V 24V 24 VDC User Supplied Power CH1 ADC CH2 ADC CH3 ADC CH4 ADC ISOLATED ANALOG CIRCUIT POWER ISOLATED ANALOG CIRCUIT COMMON INTERNAL MODULE CIRCUITRY COM COM COM COM COM COM 1 2...

Page 4: ...n your installation for use of this powerful feature 1 Align with slot 2 rotate to seated position Module Installation WARNING Do not apply field power until the following steps are completed See hot swapping procedure for exceptions WIRESTRIP LENGTH WIRESTRIP LENGTH Step One Align module catch with base slot and rotate module into connector Locked Unlocked Step Two Pull top locking tab toward mod...

Page 5: ... 1 module into the base configuration Module Configuration Wiring Options 1 ZIPLink Feed Through Modules and Cables 0 5 m 1 6 ft cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL RTB20 ZL RTB20 1 ZL P2 CBL18 ZL P2 CBL18 1 ZL P2 CBL18 2 Terminal Block with pigtail cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL P2 CBL18 1P ZL P2 CBL18 2P 3 Screw Terminal Block only P2 RTB Quantity 1 4 Spring Clamp Term...

Page 6: ... 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw input signal These values will relate to the minimum and maximum scaled values 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 The Scale Linear function can be used to Convert analog field input signals from the range which is native to the analog input module to an application specific range Mak...

Page 7: ...2 04AD 1 Fw Rev 1 00 16 BIT 0 20mA 3 CH ENABLED DISPLAY UNITS MILIAMP 0 20mA These screens will then auto cycle Error Messages An existing error will be inserted into the cycling Status Info screen This screen will auto cycle with status information 1 00000 2 00000 3 00000 4 SPARE 1 0000H 2 0000H 3 0000H 4 SPARE 1 0 00mA 2 0 00mA 3 0 00mA 4 SPARE End of Status Menu List MISSING EXTERNAL 24VDC SELF...

Page 8: ...ision Date P2 04AD 1 DS 1st Edition Rev A 2 11 2022 Copyright 2019 AutomationDirect com Incorporated All Rights Reserved Worldwide Diagnostic Status Under Range Error 1 bit per channel Over Range Error 1 bit per channel Module Failed 1 bit per module Missing 24V 1 bit per module ...

Reviews: